TIME MARK 2629 Manual Download Page 4

1.95"

DIMENSIONS 

INSTALLATION

 

 

Mount the unit in a suitable enclosure.  A NEMA-1 enclosure, designed 
for socket-mounted relays is available from Time Mark. 

 

Connect the voltage to be monitored to terminals 6 and 7. These termi-
nals are not polarity sensitive for any of the listed AC or DC models. 

Connect the load control wiring to the appropriate terminals on the 
socket:  

     For motor control applications;

 use terminals 1 and 8. 

     For phase loss alarm applications;

 use terminals 1 and 2. 

 

Insert the Model 260 into the socket and apply power.  If the contact 
does not transfer 

(green light ON)

, use  a voltmeter to insure that the 

proper voltage is present.  If voltage is correct, rotate the level 
adjustment fully counter-clockwise. The contact should transfer to 
provide a signal path between pins 1 and 8. 

 

NOTE:

 When installing the Model 260 Sensor in areas of high humidity 

or contamination, it is recommended that the base area and all 
exposed metal parts of the socket be coated liberally with a good 
quality silicon grease, such as Dow Corning DC-4 or DC-4X.  Insert the 
unit into the socket and wipe off excess grease around the base. This 
will prevent the entrance of moisture and other contaminates into the 
base and socket areas.

 

 

ADJUSTMENT PROCEDURE

 

 

The following procedure will allow the Model 260 Voltage Sensor to be 
adjusted to achieve a trip point just below the nominal voltage being 
monitored.

 

 

Rotate the adjustment control fully clockwise, or until the red 

(TRIP)

 

indicator illuminates.

 

 

On manual reset versions

, it will be necessary to hold the reset button 

down during this next step:

 

 

Slowly rotate the adjustment control in a counter-clockwise direction, 
just until the green (NORM) indicator comes on. 

WARNING 

 

IN APPLICATIONS WHERE VOLTAGES IN EXCESS OF 300 
VAC ARE TO BE MONITORED, BE CERTAIN TO USE THE 

TIME MARK MODEL 51X120

  8-PIN SOCKET, OR AN 

EQUIVALENT UL APPROVED 600VAC RATED SOCKET. 

MODEL 260 

Voltage Sensor

 

READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING  THIS DEVICE. 

KEEP THIS DATA SHEET FOR FUTURE REFERENCE. 

 

GENERAL SAFETY

 

 

POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 260.

 

ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING. 

THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL. 

 

Installation Instructions 

 

At this point, the Model 260 Voltage Sensor is the most sensitive to 

irregular power line conditions. If nuisance tripping occurs, turn the 

control slightly farther counter-clockwise.

 

 

A more accurate setting will require the use of an adjustable voltage 

source, and a voltmeter to achieve an exact setting. 

 

TROUBLESHOOTING

 

 

Should the Model 260 Voltage Sensor fail to operate properly, check 
that proper voltage is being applied to pins 6 and 7.  

On manual 

reset versions

, place a jumper across pins 3 and 4 if an external, 

normally-closed reset switch is not connected.   Should problems 
persist, contact your local Time Mark Distributor, or the factory at 
800-862-2875 

(Monday-Friday; 8 a.m. to 5 p.m. CST)

, for further 

assistance.

 

 

WARRANTY

 

 

The 

Model 260 Voltage Sensor

 is warranted to be free from defects 

in materials and workmanship, and is covered by our exclusive 

5-

year Unconditional Warranty

.   If the Model 260 fails to operate, for 

any reason, we will repair or replace it free, for five years from the 
date of purchase.  Contact the Time Mark Sales department, Monday 
through Friday; 8 a.m. to 5 p.m., CST, for further details. 

1

2 3

4
5

6

7

8

Shows contacts in 

power off 

condition 

PIN DIAGRAM 

TIME MARK is a division of

Telephone:    Main -     (918) 438-1220 
                        Sales -    (800) 862-2875

 

Fax:                                 (918) 437-7584 
 
E-mail:            [email protected] 
Internet:         http://www.time-mark.com 

Doc No. 87A133   12/00 

© 2000   

TIME MARK CORPORATION

 

11440 East Pine Street  

Tulsa, Oklahoma  74116 

TYPICAL APPLICATION 

Shows No Power Applied 

Summary of Contents for 2629

Page 1: ...ts Input voltages above the setpoint cause the output contacts to energize Input voltages below the setpoint cause the output contacts to de energize The dead band between pull in and drop out is less...

Page 2: ...allows the unit to be set to detect over voltage relay will energize on fault The L E D indicator will illuminate whenever the relay is energized NOTE When installing the Model 2629 Voltage Monitor i...

Page 3: ...ction 2500 VRMS for 10 msecs Polarity protection not required Supply current 10mA max Setpoint stability 1 Response time 100 msecs Operation Continuous duty Output contacts SPDT 10 Amps at 240 VAC res...

Page 4: ...E CERTAIN TO USE THE TIME MARK MODEL 51X120 8 PIN SOCKET OR AN EQUIVALENT UL APPROVED 600VAC RATED SOCKET MODEL 260 Voltage Sensor READ ALL INSTRUCTIONS BEFORE INSTALLING OPERATING OR SERVICING THIS D...

Page 5: ...220 Sales 800 862 2875 Fax 918 437 7584 E mail sales time mark com Internet http www time mark com Doc No 87A167 12 00 2000 TIME MARK CORPORATION 11440 East Pine Street Tulsa Oklahoma 74116 SPECIFICAT...

Page 6: ...rk Corporation s exclusive 5 Year Unconditional Warranty Should this device fail for any reason within five years from the date of purchase we will repair or replace it free Contact the Time Mark Sale...

Page 7: ...no field adjustments or calibrations to the device MODEL 2602 Nominal input voltage 120 VAC Max input voltage 135 VAC Frequency 60 Hz Power consumption 2 watts max Drop out voltage 80 VAC Pick up vol...

Page 8: ...PERATING OR SERVICING THIS DEVICE KEEP THIS DATA SHEET FOR FUTURE REFERENCE GENERAL SAFETY POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2602 ALL ELECTRICAL POWER SHOULD BE...

Page 9: ...to energize Input voltages below the setpoint cause the output contacts to de energize The dead band between pull in and drop out is less than 5 Dip switches are used on the Model 2628 to choose betwe...

Page 10: ...voltage relay will energize on fault The L E D indicator will illuminate whenever the relay is energized NOTE When installing the Model 2628 Voltage Monitor in areas of high humidity or contamination...

Page 11: ...stment range Over voltage 120 140 VAC Under voltage 90 110 VAC Response time 50 msec Line frequency 45 420 Hz Transient protection 2500V for 10 msec Contacts SPDT Contact rating 10A at 240 VAC resisti...

Page 12: ...ce WARRANTY The Model 268 Over Under Voltage Monitor is warranted to be free from defects in materials and workmanship and is covered by our exclusive 5 year Unconditional Warranty If this device fail...

Page 13: ...ltage 12vdc 24vdc 28vdc 48vdc 110vdc 230vdc Max input voltage 17vdc 32vdc 37vdc 62vdc 145vdc 270vdc Under voltage range 10 12vdc 19 24vdc 22 28vdc 38 48vdc 85 110vdc 175 230vdc Over voltage range 12 1...

Page 14: ...TROUBLESHOOTING Should the Model 2681 fail to operate properly check that voltage is present and is of the correct level Check all fuses and verify that all wiring connections are correct Should probl...

Page 15: ...sensing circuit drives an internal electro mechanical relay which is energized when the line fre quency is correct Operating power is drawn from the same line being monitored The Model 292 is set to t...

Page 16: ...mplete warranty details see the Terms and Con ditions of Sales page in the front section of the Time Mark catalog MODEL 292 Frequency Monitor READ ALL INSTRUCTIONS BEFORE INSTALLING OPERATING OR SERVI...

Page 17: ...phase Monitoring Current 1 mA max 120V per phase Voltage Adjustment Range 79 140VAC drop out pick up Frequency Adjustment Range 45 65 Hz Reset Type Automatic Repeat Accuracy 1 of full scale Output Con...

Page 18: ...ply power If the green LED is not on and the contacts do not transfer when power is applied check that all three phases are the correct voltage and are in the proper sequence A B C Check the 24VDC to...

Page 19: ...22 29vdc 25 34vdc 43 58vdc 99 135vdc 2621 ALL VERSIONS Power consumption 2 watts max Set point stability 0 5 of set point Polarity protection DC versions only Trip response 0 5 sec fixed 0 1 sec Reset...

Page 20: ...etails NOTE When installing the Model 2621 monitor in areas of high humidity or contamination it is recommended that the base area and all exposed metal parts of the socket be coated liberally with a...

Page 21: ...V Frequency 50 400 Hz Short Cycle Delay Short cycle restart delay 2 seconds R versions 5 minutes Set point Stability 1 Dead Band 1 Trip Delay 0 5 seconds fixed Contact Rating SPDT 10A at 240VAC resist...

Page 22: ...tment until the failure indicator light just illuminates and the contacts transfer Any voltage below this point will trip the relay off For over voltage sensing Slowly rotate the adjustment until the...

Reviews: