TIME MARK 2629 Manual Download Page 1

SPECIFICATIONS

 

  

Model 

2629 

Supply Voltage 

15 to 260 VAC or VDC 

Max Supply Voltage 

280 VAC or 300 VDC 

Power Consumption 

1

.

5 watts max. 

Transient Protection 

2500 V for 10 msec 

Setpoint Stability 

± 1%  

Response Time 

1 sec ON / 100 msec OFF 

Reset Type 

Automatic 

Dead Band 

less than 5% all ranges 

Contact Rating      

DPDT       5A at 240 VAC   resistive 

Expected Relay Life 

         Mech:        5 million operations 
         Elec:          100,000 at rated load 

Operating Temperature 

-13º to +122º  F 

Humidity Tolerance 

0-97% without condensation 

Enclosure Material 

ABS plastic 

Weight 

5 oz. 

Mounting 

8-pin socket   (*order separately) 

* Order 8-pin socket number 

51X120 

 

DESCRIPTION

 

 

The 

Model  2629 AC/DC Voltage Monitor

 is designed 

to continuously monitor any AC or DC voltage from 15 
to 260 volts.

 

 

Input voltages above the setpoint cause the output 
contacts to energize.  Input voltages below the setpoint 
cause the output  contacts to de-energize.  The dead 
band between pull-in and drop-out is less than 5%.

 

 

Dip switches are used on the Model  2629  to choose 
between AC and DC voltage monitoring, and to select 
one of the eight trip level ranges.  Each trip level has a 
user adjustable  35 volt range, with a 5 volt overlap 
between the ranges.  The unit has a screwdriver 
adjustment to set the trip point within that 35 volt range. 

l

l

  Monitors Over or Under Voltage  

l

l

 AC or DC from 15 to 260 Volts 

l

l

 Adjustable Trip Points 

l

l

 Automatic Reset 

l

l

 DPDT Relay 

MODEL 2629 

AC/DC 

Voltage Monitor 

TIME MARK is a division of

Telephone:    Main -     (918) 438-1220 
                      Sales -    (800) 862-2875

 

Fax:                              (918) 437-7584 
 
E-mail:          [email protected] 
Internet:        http://www.time-mark.com 

11440 East Pine Street  

Tulsa, Oklahoma  74116 

DIMENSIONS 

01/02 

TYPICAL APPLICATION 

Summary of Contents for 2629

Page 1: ...ts Input voltages above the setpoint cause the output contacts to energize Input voltages below the setpoint cause the output contacts to de energize The dead band between pull in and drop out is less...

Page 2: ...allows the unit to be set to detect over voltage relay will energize on fault The L E D indicator will illuminate whenever the relay is energized NOTE When installing the Model 2629 Voltage Monitor i...

Page 3: ...ction 2500 VRMS for 10 msecs Polarity protection not required Supply current 10mA max Setpoint stability 1 Response time 100 msecs Operation Continuous duty Output contacts SPDT 10 Amps at 240 VAC res...

Page 4: ...E CERTAIN TO USE THE TIME MARK MODEL 51X120 8 PIN SOCKET OR AN EQUIVALENT UL APPROVED 600VAC RATED SOCKET MODEL 260 Voltage Sensor READ ALL INSTRUCTIONS BEFORE INSTALLING OPERATING OR SERVICING THIS D...

Page 5: ...220 Sales 800 862 2875 Fax 918 437 7584 E mail sales time mark com Internet http www time mark com Doc No 87A167 12 00 2000 TIME MARK CORPORATION 11440 East Pine Street Tulsa Oklahoma 74116 SPECIFICAT...

Page 6: ...rk Corporation s exclusive 5 Year Unconditional Warranty Should this device fail for any reason within five years from the date of purchase we will repair or replace it free Contact the Time Mark Sale...

Page 7: ...no field adjustments or calibrations to the device MODEL 2602 Nominal input voltage 120 VAC Max input voltage 135 VAC Frequency 60 Hz Power consumption 2 watts max Drop out voltage 80 VAC Pick up vol...

Page 8: ...PERATING OR SERVICING THIS DEVICE KEEP THIS DATA SHEET FOR FUTURE REFERENCE GENERAL SAFETY POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 2602 ALL ELECTRICAL POWER SHOULD BE...

Page 9: ...to energize Input voltages below the setpoint cause the output contacts to de energize The dead band between pull in and drop out is less than 5 Dip switches are used on the Model 2628 to choose betwe...

Page 10: ...voltage relay will energize on fault The L E D indicator will illuminate whenever the relay is energized NOTE When installing the Model 2628 Voltage Monitor in areas of high humidity or contamination...

Page 11: ...stment range Over voltage 120 140 VAC Under voltage 90 110 VAC Response time 50 msec Line frequency 45 420 Hz Transient protection 2500V for 10 msec Contacts SPDT Contact rating 10A at 240 VAC resisti...

Page 12: ...ce WARRANTY The Model 268 Over Under Voltage Monitor is warranted to be free from defects in materials and workmanship and is covered by our exclusive 5 year Unconditional Warranty If this device fail...

Page 13: ...ltage 12vdc 24vdc 28vdc 48vdc 110vdc 230vdc Max input voltage 17vdc 32vdc 37vdc 62vdc 145vdc 270vdc Under voltage range 10 12vdc 19 24vdc 22 28vdc 38 48vdc 85 110vdc 175 230vdc Over voltage range 12 1...

Page 14: ...TROUBLESHOOTING Should the Model 2681 fail to operate properly check that voltage is present and is of the correct level Check all fuses and verify that all wiring connections are correct Should probl...

Page 15: ...sensing circuit drives an internal electro mechanical relay which is energized when the line fre quency is correct Operating power is drawn from the same line being monitored The Model 292 is set to t...

Page 16: ...mplete warranty details see the Terms and Con ditions of Sales page in the front section of the Time Mark catalog MODEL 292 Frequency Monitor READ ALL INSTRUCTIONS BEFORE INSTALLING OPERATING OR SERVI...

Page 17: ...phase Monitoring Current 1 mA max 120V per phase Voltage Adjustment Range 79 140VAC drop out pick up Frequency Adjustment Range 45 65 Hz Reset Type Automatic Repeat Accuracy 1 of full scale Output Con...

Page 18: ...ply power If the green LED is not on and the contacts do not transfer when power is applied check that all three phases are the correct voltage and are in the proper sequence A B C Check the 24VDC to...

Page 19: ...22 29vdc 25 34vdc 43 58vdc 99 135vdc 2621 ALL VERSIONS Power consumption 2 watts max Set point stability 0 5 of set point Polarity protection DC versions only Trip response 0 5 sec fixed 0 1 sec Reset...

Page 20: ...etails NOTE When installing the Model 2621 monitor in areas of high humidity or contamination it is recommended that the base area and all exposed metal parts of the socket be coated liberally with a...

Page 21: ...V Frequency 50 400 Hz Short Cycle Delay Short cycle restart delay 2 seconds R versions 5 minutes Set point Stability 1 Dead Band 1 Trip Delay 0 5 seconds fixed Contact Rating SPDT 10A at 240VAC resist...

Page 22: ...tment until the failure indicator light just illuminates and the contacts transfer Any voltage below this point will trip the relay off For over voltage sensing Slowly rotate the adjustment until the...