neighbors as well as the green plants.
Requirements of the mounting structure:
The mounting rack must meet the relevant national or industrial standards in terms of
strength with welding and connection areas rustproofed.
The mounting rack and its load carry surface shall be able to withstand 4 times or above
the weight of the unit.
The mounting rack of the outdoor unit shall be fastened with expansion bolt.
Ensure the secure installation regardless of what type of wall on which it is installed, to
prevent potential dropping that could hurt people.
Electrical Safety Requirements:
Be sure to use the rated voltage and air conditioners dedicated circuit for the power supply,
and the power cable diameter must meet the national requirements.
If the rated current of the device is greater than or equal to 16A, it is necessary to use a
connection to the mains with the organization of an individual line and install an ELCB. For
the connecting line, a cable with a cross section of 1.5-2 mm
2
and circuit breakers are
used.
The minimum clearance between the air conditioner and the combustibles is 1.5 m.
The interconnection cord enables connect the indoor and outdoor units. You must first
choose the right cable size before preparing it for connection.
Cable Types:
Indoor Power Cable (if applicable): H05VV-F;
Interconnection cord: H07RN-F or H05RN-F;
Minimum Cross-Sectional Area of Power Cable and Interconnection cord:
Rated Current
of Appliance (A)
Nominal Cross-
Sectional Area
(mm
2
)
>
3 and ≤ 6
0.75
>
6 and ≤10
1
>
10 and ≤16
1.5
>
16 and ≤25
2.5
>
25 and ≤32
4
>
32 and ≤40
6
The size of the interconnection cord, power cable, fuse, and switch needed is determined
by the maximum current of the unit.
The maximum current is indicated on the nameplate located on the side panel of the unit.
Refer to this nameplate to choose the right cable, fuse, or switch.
Summary of Contents for Natt T-AC07-S29-X
Page 12: ...IM2020 12 Fig 10 4 Put wiring cover back and then tighten the screw 5 Close the panel Fig 11...
Page 21: ...IM2020 21 T AC24 S29 Y T AC07 S29 X T AC09 S29 X T AC12 S29 X T AC18 S29 X...
Page 26: ...IM2020 26 1 2...
Page 27: ...IM2020 27...
Page 28: ...IM2020 28 0 C 2 7000 9000 12000 18000 BTU 24000 30000 36000 BTU 3 4 1 16 C 48 C 32 C 10 C 32 C...
Page 29: ...IM2020 29 5 1 1 2 3 4 5 6 7 8 9 10 11 auto 12...
Page 32: ...IM2020 32 4 16 1 5 2 2 1 5 H05VV F H07RN F H05RN F 2 3 6 0 75 6 10 1 00 10 16 1 50 16 25 2 50...
Page 33: ...IM2020 33 2 I 2 1 2...
Page 34: ...IM2020 34 3 3 4 3 5 10 4 4 60 80...
Page 35: ...IM2020 35 5 6 5 6 1 2 7...
Page 36: ...IM2020 36 7 1 2 3 1 2 3 8...
Page 37: ...IM2020 37 1 2 9 1 ee 2 3 4 5 10...
Page 38: ...IM2020 38 11 12 5 5 15 12000 BTU 20 18000 BTU 30...
Page 39: ...IM2020 39 13 1 2 3 4 5 14...
Page 40: ...IM2020 40 15 R410A 1 2 3 LO 15 0 1 76cmHg 4 5 16...
Page 41: ...IM2020 41 9 on off 17 19...
Page 45: ...IM2020 45...
Page 46: ...IM2020 46 12 T AC07 S29 Y T AC09 S29 Y T AC12 S29 Y T AC18 S29 Y T AC24 S29 Y...
Page 47: ...IM2020 47 T AC07 S29 X T AC09 S29 X T AC12 S29 X T AC18 S29 X T AC24 S29 X...
Page 48: ...IM2020 48 13...
Page 49: ...IM2020 49...
Page 50: ...IM2020 50 LIGHT 7000 9000 12000 18000 BTU 24000 30000 36000 BTU 14...
Page 51: ...IM2020 51 15 30 C 50 C 15 85 5...
Page 52: ...www timberk ru...