10. Technical data
19
Nominal voltage range:
50 ... 36 000 V AC/DC
Frequency:
0 ... 200 Hz
Input resistance:
105 MΩ in the moulded resistance cartridge
beneath the test electrode
Measurement current:
< 0.9 mA at 36 000 V AC/DC
Surge voltage strength:
> 200 kV (test report available)
Indicator group:
I and III
Limit Ut:
The value of the response voltage Ut is labelled on the name plate.
Display:
red LED for voltage > Limit Ut
green LED for standby / absent of voltage
360° LED light-stripe red / green
two-line LCD with backlight green / red for indication of voltage,
frequency, type of voltage, and battery condition
acoustic signal at > Limit Ut
Measurement range / limit deviation:
50 ... 1000 V AC/DC ± 5% + 10 Digits
1,01 … 9,99 kV AC/DC ± 5% + 10 Digits
10,1 … 36,0 kV AC/DC ± 5% + 10 Digits
On-time:
5 minutes
Construction:
for indoor and outdoor installations
Operating temperature:
–15°C … + 55°
Self-test:
function, protective resistors and ground contact
Power supply:
6 x AA 1,5 V - IEC LR6 alkali-manganese or FR6 Lithium battery
Protection category:
IP 65, device can be used in moist environments
Design:
• two-pole voltage tester with fixed connection to ground
• 4-part GRP-telescopic tube with integrated PUR spiral line
(Type TT 36-8m 6-part GRP-telescopic tube)
• moulded resistor decade approx. 105 MΩ
• display part made of impact-proof, dust proof
plastic casing IP 65 with unbreakable display cover
• connection-line PUR with clamp for railfoot or universal clamp or contact
magnet for grounding at rails
(various length and versions)
Standards
EN/IEC 61243-2 high voltage tester
EN/IEC 60071 Surge voltage strength
(further details see risk analysis)
Test label:
date of the next examination on the sticker
repeated inspection at least every 6 years
Dimensions / weight
1740 x 120 x 110 mm
run-out length up to 5.2 m (Type TT 36-8M up to 7.2 m)
complete device incl. line and contact clamp 4.0 kg