7
Adjust 4mA For CPF XX.XXmA
Adjust 20mA For CPF XX.XXmA
Status Contact Output OUT1
~
OUT6
Extended Contact Output OUT7
~
OUT10
Feedback Password Change XXX
Feedback Password
XXX
Feedback Set
Enter?
4.1.7 Resume Default
:
While user needs to reset this item
,
this item can be used to reset factory setting, except for
“Accept Valve close Limit”
、
“Accept Valve open Limit” and “The Valve Close Direction”.
4.2 Feedback set
After Choosing “Feedback set” and press “Ok”, if password is 0,it directly goes into next menu, otherwise user
needs to input feedback password to go into next menu.
4.2.1 Adjust 4mA For CPF: When user thinks that 4mA current is inaccurate, user can use this item to increase or
decrease feedback current.
4.2.2 Adjust 20mA For CPF: When user thinks that 20mA current is inaccurate, user can use this item to increase
or decrease feedback current.
4.2.3 Status Contact Output: OUT1
~
OUT5 are relays which indicate valve status
(
that is, S1
~
S4 and contact R
in the electric schematic diagram
)
and each contact only represents one status. In the following status, user can
choose weather the contact closes or opens. These status include: Fully Closed
、
Fully Open
、
Over Torque Close
、
Over Torque Open
、
Over Torque
、
Closing
、
Opening
、
Running
、
Middle Position
(
≥
xx%
)、
Remote Mode
、
Local
Mode. Factory setting: OUT1(S1):Fully Open, Closure; OUT2(S2):Fully Close, Closure; OUT3(S3):over-Torque
Open, Closure; OUT4(S4):Over Torque Open, Closure; OUT5(R): Remote Mode, Closure.
OUT6 is overall alarm relay (that is the contact MONI showed in the electric schematic diagram). If “CPU
Error”
、
“ROM Error”
、
“RAM Error”
、
“A/D Error”
、
“Lost Phase”
、
“Lost Analog”
、
“OP.& CL.SIG.ON”
、
“MOT.
Over Thermal” display and set up parameters
,
this contact will close
(
if off-contact is needed, please notify when
making an order
)
. Besides, press “Ok” to go into OUT6 sub menu to choose if that alarm includes “Over
Torque”
、
“At Remote”, Factory setting: “Over Torque”, without “At Remote”.
4.2.4 Extended Contact Output
(
Non-standard option. Please notify when placing an order
):
OUT7
~
OUT10 are relays which indicate valve status
,
and one contact only can represent one status. In the
following status, user can choose weather the contact closes or opens. These status includes
:
Fully Closed
、
Fully
Open
、
Over Torque Close
、
Over Torque Open
、
Over Torque
、
Closing
、
Opening
、
Running
、
Middle Position
(
≥
xx%
)、
Remote Mode
、
Local Mode.
4.2.5 Feedback Password Change
:
After choosing this item
,
on the right side there will be the password which can
be set in the range of 0-255, press “Ok” to save. Factory setting
:
0.
4.3
Advanced Settings
ESD Control
Disable / Enable
BUS Control Enter?
Close Seating Position / Torque
The Valve Close Direction Closewise/Anti-Closewise
Polarity For ACC. 4mA=Fully Closed/Fully Open
Polarity For CPF. 4mA=Fully Closed/Fully Open
Two-Wire Control Disable/Open First/Close First
Calibrate 4mA For ACC. XX.XXmA
Calibrate 20mA For ACC. XX.XXmA
Brake Time 0~50ms
Stop Moving Time Before Brake 100~250ms
Two-Speed Timer Control
Disable / Enable
Senior Password Change 0~255
Basic Password Inquires 0~255
Feedback Password Inquires 0~255
Set The Default Value Enter
?
Advanced
Password
25
Advanced Settin
gs
Enter?