5
After powering up and initialization, valve position in big size font is displayed on the whole LCD. At fully-open
position and fully closed position, valve position of butterfly valve is shown in the following pictures.
Valve position display Fully open Fully closed Main menu
3.Adjustment for electric actuator
Note: 1. If user do not press any button on the remote setter in one minute, LCD display will be
back to valve position display. Besides, press “Esc” to escape after setup is finished and valve
position percentage is shown on LCD.
2. The moment it goes into setup interface, first-shown percentage value is the one which is
set last time. User can see the previous setup-value through this way.
3.1 Setup in the menu
:
Turn status selector switch at “Local”. Press “Ok” key to enter main menu. Or, turn status selector switch at
“Stop”, and operation selector switch at “Open” in three seconds, then it goes into the main menu.
3.2Confirm rotation direction
:
User shall confirm if the rotation direction of valve and actuator are the same. Closing direction for actuator
before dispatched is clockwise. If this is not the same as that of valve, please go to main menu to set up the closing
direction of actuator is same as that of valve. Operating steps are as follows:
Follow 3.1 to go into main menu, and press “Down” key to choose < Advanced Settings>, press “Ok” to go into
<Advanced password>, input factory password“25”, press “Ok” key to go into next menu
,
press “Down” key and
choose <The Valve Close Direction>, press “Open” or “Close” to choose “counterclockwise”, press “ok” to save.
3.3 Setup for limit position
Note: 1. User can set up fully-closed position first and then fully-open position and vice versa.
Setup methods are the same.
2. Encoder value 0 and 65535 respectively are the minimum value and maximum value.
The two overlaps. While setting up open/close limit, it can go through this overlapped position.
But it shall make sure that the value in the whole limit shall be in the range of absolute encoder
value range (0-65535).
3. Follow the steps in 3.3.1 or 3.3.2, otherwise it will alarm “Overload”.
3.3.1 Set up limit position by remote setter
①
Turn status selector switch at “Local”
,
and press “Ok” to go into main menu.
②
Choose “Basic Settings”
,
input password and go into next menu
(
password is“0” before dispatched
,
skip “The
basic password” page
)
. After choosing “Accept Valve Close Limit”
,
on the right side there is the timely-position’s
encoder.
③
Make the valve to turn at limit closing position by using handwheel
,
or press “Open”/“Close” on the remote
setter to make valve to turn at limit closing position.
④
Press “Ok” to save
,
the red indicator above LCD starts to blink first and then light up, which means that
position is set up as limit closing position.
⑤
Make the valve to turn at limit open position by using handwheel, or press “Open”/“Close” on the remote
setter to make valve to turn at limit open position.
⑥
Press “Down” key to choose “Accept Valve open Limit”
,
press “Ok” to save
,
the green indicator above the
LCD starts to blink 2 times and then light up
,
which means that position is set up as open limit position.
⑦
After setting up, press “Esc” to go back to valve position interface.
Note: if press “Esc” before pressing “Ok” key to save, Open/Close limit is not set up. The
Basic Settings Enter
?
Feedback Set
Advanced Settings
Signal Inquires
Closing
56.1%
Local Inching
Remote Manual
At Rest
At Rest
Remote