Instruction Manual for Installation and Application of JTW-ZOM-TC5162 Addressable Rate of Rise and Fixed Temperature Heat

Detector

Check whether there is short circuit in the thermistor.

IX Maintenance

1. The detector should be installed just before commission and kept well before installation, taken

corresponding measures for dust-proof, damp-proof and corrosion-proof.

2. The dust-proof cover should not be removed until the project plunged into usage.
3. Clean the detectors regularly, at least once a year to ensure normal operation of the system.
4. Before cleaning, notify the proper authorities that the system is under maintenance and will temporarily

be out of service. Disable the automatic controls relating to the zone or system under maintenance to
avoid unwanted actions.

5. The detector should be tested after re-installed to ensure normal operation.
6. Fire simulation test should be done to the detector at least every 6 months.

X Cautions

1. There should be no barrier around the detector within 0.5m.
2. The horizontal distance between detector and the air conditioner’s outlet should be at least 1.5 meters.
3. The horizontal distance between detector and wall, and edge beam should be at least 0.5 meters.
4. The detector shall be horizontally installed. If it has to be installed on an inclined plane, the inclination

angle shall not be over 45º.

5. The base should be fixed firmly, and reliable wiring.
6. During maintenance, personals should be careful to avoid damage to the detector.
7. Used in internal corridor’s ceiling and the width of internal corridor is less than 3m, heat detector should

be arranged centered, and the mounting distance should not be more than 10m.

8. Heat detector should not be used in places where may produce smoldering fire.

XI Packaging Document and Maintenance

1 Packaging document: packaging list: one

China·Liaoning·Yingkou Tiancheng Fire Protection Equipment Co., Ltd.

6

Summary of Contents for JTW-ZOM-TC5162

Page 1: ...d application of the product please read the Instruction Manual for Installation and Application Instruction Manual for Installation and Application of JTW ZOM TC5162 Addressable Rate of Rise and Fixed Temperature Heat Detector Ver 2 0 YINGKOU TIANCHENG FIRE PROTECTION EQUIPMENT CO LTD China Liaoning Yingkou Tiancheng Fire Protection Equipment Co Ltd 1 ...

Page 2: ...s such as indoor garages kitchens boiler rooms generator rooms drying rooms power generation dehydrating workshop etc II Features 1 Non polarized signal 2 wire 2 The detector can be addressed in field by using Hand Held Encoder easy and reliable for commissioning 3 Thermal sensitive element improves the response speed of temperature variation III Technical Specifications 1 Class A2R 2 Operating vo...

Page 3: ... 110g 6 Mounting hole distance 60mm 7 Standard EN 54 5 2017 A1 2018 IV Structure and Operation Principle 1 Appearance of the detector is shown in Fig 1 Fig 1 2 Operation principle The detector uses thermistor as its sensor and transmits the signal to a single chip which after voltage transfer processes the signal using intelligent arithmetic and sends any fire alarm to the FACP The LED indicators ...

Page 4: ...op to terminals polarity insensitive After the base is fixed firmly rotate the bottom of detector and base clockwise and then the detector will be fitted to the base Fig 3 3 Recommended Wiring 1 0mm2 or above fire cable subject to local codes 4 Warning Before testing please ensure that the detector has been installed correctly and powered up VI Testing 1 The detector must be tested after installat...

Page 5: ...erminal non polarity and write or read the address code 2 Coding step press 2 in the main menu of the encoder to enter into 2 mode setup and choose 1 TC5000 in the sub menu Press 5 6 or 7 to choose ascending number coding normal coding or descending number coding Easy application default is TC5000 normal coding and chosen complete press erase roll page to enter into coding interface and press exit...

Page 6: ...operation 6 Fire simulation test should be done to the detector at least every 6 months X Cautions 1 There should be no barrier around the detector within 0 5m 2 The horizontal distance between detector and the air conditioner s outlet should be at least 1 5 meters 3 The horizontal distance between detector and wall and edge beam should be at least 0 5 meters 4 The detector shall be horizontally i...

Page 7: ...points X Limited Warranty 1 Tiancheng warrants that the product will be free of charge for repairing or replacing from defects in design materials and workmanship during the warranty period This warranty shall not apply to any product that is found to have been improperly installed or used in any way not in accordance with the instructions supplied with the product Anybody including the agents dis...

Page 8: ...t Detector China Liaoning Yingkou Tiancheng Fire Protection Equipment Co Ltd Add No 11 2 Kechechang Xili Xishi District Yingkou Pilot Free Trade Zone Liaoning China Tel 86 417 3553119 Post Code 115004 E mail info tcfiretech com Website www tcfiretech com China Liaoning Yingkou Tiancheng Fire Protection Equipment Co Ltd 8 ...

Reviews: