Check whether there is short circuit in the thermistor.
IX Maintenance
1. The detector should be installed just before commission and kept well before installation, taken
corresponding measures for dust-proof, damp-proof and corrosion-proof.
2. The dust-proof cover should not be removed until the project plunged into usage.
3. Clean the detectors regularly, at least once a year to ensure normal operation of the system.
4. Before cleaning, notify the proper authorities that the system is under maintenance and will temporarily
be out of service. Disable the automatic controls relating to the zone or system under maintenance to
avoid unwanted actions.
5. The detector should be tested after re-installed to ensure normal operation.
6. Fire simulation test should be done to the detector at least every 6 months.
X Cautions
1. There should be no barrier around the detector within 0.5m.
2. The horizontal distance between detector and the air conditioner’s outlet should be at least 1.5 meters.
3. The horizontal distance between detector and wall, and edge beam should be at least 0.5 meters.
4. The detector shall be horizontally installed. If it has to be installed on an inclined plane, the inclination
angle shall not be over 45º.
5. The base should be fixed firmly, and reliable wiring.
6. During maintenance, personals should be careful to avoid damage to the detector.
7. Used in internal corridor’s ceiling and the width of internal corridor is less than 3m, heat detector should
be arranged centered, and the mounting distance should not be more than 10m.
8. Heat detector should not be used in places where may produce smoldering fire.