8
SME70, SME70-C, SME70-M-Manual-04-2020
INPUT CIRCUITS
—
Auxiliary power supply Uaux
Rated voltage
24 V-
Nominal value (range)
19.2...28.8
V-
Max alternating component
10%
Maximum time at power ON
0.10 s
Power consumption at rest condition
2.5 W
Max power consumption
<3
W
—
Rated frequency
f
n
Rated value
50, 60 Hz (sw setting)
Range
47.5...51.5 Hz (
f
n
= 50 Hz)
57.5...61.5 Hz (
f
n
= 60 Hz)
—
Sensor inputs
Current transformers
Type
Rogowski open core
Coupling Bayonet
Inside diameter
95 mm
Rated transformation ratio
1000 A/0.100 V
Bandwidth
40 Hz...20 kHz
Connection to SME70
• type
bipolar shielded wires
• section
0.15 mm
2
• length
3.5 m
Voltage inputs
Type
Capacitive voltage dividers
Plug
DY811
MV rated voltage
6...36 kV
Capacitive reactance (MTV side)
100...700 MΩ
Connection to SME70
• type
shielded wires
• section
0.5 mm
2
• length
3.0 m
—
Binary input
Quantity 1
Type
optocoupler
Operative range rated
U
aux
Max consumption, energized
3
mA
OUTPUT CIRCUITS
—
Relays
Quantity 3
Type of contacts
make (SPST-NO, type A)
Nominal current
2 A
Nominal voltage
250 V
Breaking capacity (24 V, L/R = 40 ms)
0.2 A
Minimum switching load
300 mW (5 V/5 mA)
Each output relay is independently programmable as normally energized or de-energized (
ENER-
GIZED/DE-ENERGIZED
)
—
Current converter
Operating range
100...900 A (step 10 A)
Output current
4...20 mA
With 67N element active inside the no trip sector
0 mA
Accuracy
10%
Max load
750 Ω
Maximum response time
300 ms
CONNECTION TO THE REMOTE CONTROL UNIT
Type
9 wires multipolar cable
Section 1
mm
2
Length 8
m