TECHNICAL DATA
Inverse time
[1]
First threshold inverse time (
I
2
>
inv
)
0.03...1.00
I
B
(step 0.01
I
B
)
First threshold
within CLP (
I
2CLP>inv
)
0.03...5.00
I
B
(step 0.01
I
B
)
Operating time (
t
2
>
inv
)
0.02...60.0
s
0.02...9.99 s (step 0.01 s)
10.0...60.0 s (step 0.1 s)
I
2
>>
Element
CLP mode (
I
2CLP
>>
Mode)
OFF/ON-Element blocking/ON-Change setting
CLP activation time (
t
2CLP
>>)
0.00...100.0
s
0.00...9.99 s (step 0.01 s)
Reset time delay (
t
2
>>
RES
)
0.00...100.0 s (step 0.1 s)
0.00...9.99 s (step 0.01 s)
10.0...100.0 s (step 0.1 s)
Defi nite time
Second threshold defi nite time (
I
2
>>
def
) 0.10...1.00
I
B
(step 0.01
I
B
)
Second
threshold within CLP (
I
2CLP>>def
) 0.10...5.00
I
B
(step 0.01
I
B
)
Operating time (
t
2
>>
def
)
0.03...10.00 s (step 0.01 s)
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot
time
0.04
s
Pickup accuracy
1% with
I
2
≥ 0.5
I
n
Operate time accuracy
5% or ± 10 ms
Phase rotation direction check - 47
47 Element
Defi nite time
Threshold (
U
s1
<
) 0.05...0.30
E
n
Threshold (
U
s
>
)
0.70...1.00
U
n
Pickup time
≤
0.04 s
Dropout
ratio
0.95...0.98
Dropout time
≤
0.05 s
Overshoot
time
0.04
s
Pickup
accuracy ±
0.5% on current measures
±
0.5% on voltage measures
Operate time accuracy
5% or ± 10 ms
Thermal image for Motor/generator protection - 49MG
Common confi guration:
Initial thermal image
(
Dth
IN
)
0.0...1.0
Δθ
B
(step 0.1
Δθ
B
)
[2]
Starting overload coeffi cient (
K
ST
)
1.0...3.0
(step
0.1)
Negative sequence current heating coeffi cient (
K
2
)
0...10 (step 1)
Heating time constant (
T+
)
1...200 min (step 1 min)
Cooling time constant (
T-
)
1.0...6.0
τ
+ (step 0.1
τ
+)
CLP operating mode (
Dth
CLP Mode
)
OFF/Blocking/Change
setting
CLP activation time (
t
DthCLP
)
0.00...200
s
0.00...9.99 s (step 0.01 s)
10.0...99.9 s (step 0.1 s)
100...200 s (step 1 s)
DthAL1 Element
First alarm threshold
(
Dth
AL1
)
0.3...1.0
Δθ
B
(step 0.1
Δθ
B
)
DthAL2 Element
Second alarm threshold
(
Dth
AL 2
) 0.5...1.2
Δθ
B
(step 0.1
Δθ
B
)
Dth> Element
Trip threshold (
Dth
>)
0.800...1.500
Δθ
B
(step 0.001
Δθ
B
)
Pickup
accuracy ±
0.5% with 0.1
I
n
, ±
0.2% with 1
I
n
Operate time accuracy
5% or ± 10 ms
Note 1
Standard Inverse Time (IEC 255-3/BS142 type A or SIT):
t = 0.14 · t
2
>
inv
/ [(I
2
/I
2
>
inv
)
0.02
- 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT):
t = 13.5 · t
2
>
inv
/ [(I
2
/I
2
>
inv
) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT):
t = 80 · t
2
>
inv
/ [(I
2
/I
2
>
inv
)
2
- 1]
Moderately Inverse (ANSI/IEEE type MI):
t = t
2
>
inv
· {0.01 / [(I
2
/I
2
>
inv
)
0.02
- 1] + 0.023}
Very Inverse (ANSI/IEEE type VI):
t = t
2
>
inv
· {3.922 / [(I
2
/I
2
>
inv
)
2
- 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI):
t = t
2
>
inv
· {5.64 / [(I
2
/I
2
>
inv
)
2
- 1] + 0.024}
I-squared-t
(I
2
t = K):
t = 16 · t
2
>
inv
/ (I
2
/I
2
>
inv
)
2
Electromechanical (EM):
t = 0.28 · t
2
>
inv
/ [-0.236 · (I
2
/I
2
>
inv
)
-1
+ 0.339]
RECTIFIER (RI):
t = 2351 · t
2
>
inv
/ [(I
2
/I
2
>
inv
)
5.6
- 1]
t
:
operate time, minimum operate time:
0.1 s
I
2
>
inv
:
pickup value
t
2
>
inv
:
operate time setting
Asymptotic reference value:
1.1
I
2
>
inv
Equation is valid for 1.1 ≤ I
2
/I
2
>
inv
≤ 20, the upper limit is
50
I
n
Note 2
Δθ
is the thermal image (p.u. of the basic over temperature corresponding to the basic current
I
B
).
Assuming that the secondary rated current of the line CT’s equals the rated current of the relay, as usually happens, the I
B
value is the ratio
between the rated current of the protected element and the CT’s primary rated current
—
—