16
NVA100X-D - Manual - 02 - 2016
TECHNICAL DATA
3.3 OUTPUT
CIRCUITS
Relays
Quantity 8
or
16
[1]
Type
KC1-1, KC1-2, KC1-7, KC1-8, KC2-1, KC2-2, KC2-7, KC2-8
changeover (SPDT, type C)
KC1-3, KC1-4, KC1-5, KC1-6, KC2-3, KC2-4, KC2-5, KC2-6
make (SPST-NO, type A)
Rated
current
8
A
Short duration current (0,5 s)
30 A
Rated voltage/max switching voltage
250 V~/400 V~
Make 1000
W/VA
Minimum switching load
300 mW (5 V/ 5 mA)
Life
Mechanical
10
6
Electrical
10
5
Breaking capacity:
Direct current (L/R = 40 ms)
50 W
Alternating current (
λ
= 0,4)
1250 VA
Minimum pulse width
0....500 ms (step 5 ms)
Block output (Logic selectivity)
Quantity
1
Type
optocoupler
3.4
MMI (MAN MACHINE INTERFACE)
Display
128 x 64 graphic LCD
LEDs
Numero
16
ON/fail (verde)
1
Start (giallo)
1
Trip (rosso)
1
Programmabili (rosso)
13
Keyboard
8
keys
3.5 COMMUNICATION
INTERFACES
Local port
Ethernet
100
Base
TX
Baud rate
230400 bps
Protocol
ModBus®TCP/IP
Connector
RJ45
Remote ports
RS485
Connection
screw
terminals
Baud rate
1200...57600 bps
Protocol
[2]
ModBus®RTU
IEC
60870-5-103
DNP3
Ethernet 100BaseT
Connection
[3]
Optical fi ber 1300 nm, ST
100 Base TX, RJ45
Baud rate
100 Mbps
Protocol
ModBus®TCP/IP, IEC51850 Level A
Enable Delayed Trip
[4]
ON/OFF
Delayed Trip delay time
0.00...10.00 s (step 0.01 s)
Note 1 The quantity of binary inputs and output relays (8+8 relè di comando o 8 relè di c16 relè di segnalazione) depend on the version that
must be specifi ed at ordering
Note 2 Different version must be selected at ordering
Note 3 Different version must be selected at ordering; two redundant port selectable with TX (RJ45) or FX (fi ber) connections or two ports with TX
(RJ45) connections. The secondary port is activated in the event of failure of the primary port or by means of hw-sw switching command
Note 4 Parameters concern the IEC61850 protocol. Settings are available inside the Set \ Base menu.
—
•
•
•
•
•
•
—
•
•
•
•
—
•
•
•
—
•
•
•
•
•
•
•
•