![Thytronic NV10B Manual Download Page 111](http://html1.mh-extra.com/html/thytronic/nv10b/nv10b_manual_1113996111.webp)
APPENDIX
111
NV10B - Manual - 04 - 2022
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59 First threshold inverse time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>inv Operating time
tU>inv
s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
U>> Element
Setpoints
U>> Logical block
U>>BLK1
OFF | ON
U>> Breaker failure
U>>BF
OFF | ON
U> Disabling by U>> start
U>disbyU>>
OFF | ON
U>> Start relays
U>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Trip relays
U>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
U>> Start LEDs
U>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
U>> Trip LEDs
U>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59 Second threshold definite time
State
OFF | ON
Pickup value
Un
0.50 ... 1.50 step = 0.01
U>>def Operating time
Value
s
0.03 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Residual overvoltage - 59N
Common configuration
Residual voltage measurement type for 59N - direct/cal-
culated
3VoType59N
UE | UEC
59N Operation from 74VT external
74VText59N
OFF | Block
UE> Element
Setpoints
UE> Enable
UE> Enable
OFF | ON
UE> Curve type
UE>Curve
INVERSE | DEFINITE
UE> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE> Logical block
UE>BLK1
OFF | ON
UE> Breaker failure
UE>BF
OFF | ON
UE> Start relays
UE>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Trip relays
UE>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Start LEDs
UE>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
UE> Trip LEDs
UE>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Definite time
59N First threshold definite time
State
OFF | ON
Pickup value
UEn
0.01 ... 0.70 step = 0.01
UE>def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59N First threshold inverse time
State
OFF | ON
Pickup value
UEn
0.01 ... 0.50 step = 0.01
UE>inv Operating time
tUE>inv
s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Element