9
Testing
&
Commissioning
G.
1.
Check the burner operating pressure. It is taken at the Manifold Pressure Test Point, with two
(2) burners operating at “High Flame” setting.
2.
Remove the knobs/dials, and open the front panel cover.
3.
Remove the plug from the Manifold Pressure Test Point. Install a portable manometer on the
Manifold Pressure Test Point. Check for gas leak on the connection.
4.
Turn ON the isolation gas valve, and open two (2) burners set at “High Flame”.
5.
Check the pressure reading in the manometer. The manometer pressure reading should be
according to the pressure of the gas type indicated in the rating label and on the Gas
Specification Table on page 5 of this manual.
6.
Once the burner operating pressure had been confirmed to be within the requirement, turn
OFF the burner and pilot, shut off the isolation gas valve, and remove the portable manometer
from the Manifold Pressure Test Point, and return the plug. Then, check for gas leak after
returning the plug.
7.
Return the front panel cover, and the control knobs.
8.
Do not leave the premises until the functions of the following were fully checked and
functional:
a.
Lighting of the Pilot burners
b.
Lighting of the Main burners
c.
Setting of the “Low Flame”
d.
Turning OFF of the Main burners
e.
Turning OFF of the Pilot burners
Note that the procedure of the above processes is specified in the “Operation Guide” section
of this manual.
9.
The owner of the equipment must keep this manual along with the records of the purchase
and installation of the equipment for future reference.
10.
It is essential that the operator/user was instructed for the correct procedure for lighting,
operation and shutdown of the equipment.
Manifold Pressure
Test Point