Trouble Shooting
CONVERTING FROM LPG TO NG AND VICE-VERSA:
1. Turn-off the pilot.
2. Shut-off the main isolation valve and follow the
lock-out/tag-out procedure.
3. Remove the gas regulator.
4. Remove the converter cover from the regulator.
Use a 22mm spanner.
5. Pull-out the converter and position it to your
desired gas type.
6. Install the converter cover to the regulator.
7. Re-install the regulator to the unit. Follow the
direction of the arrow on the regulator when
installing.
8. Replace the main burner injector Follow the main
burner injector removal procedure. See table
below for injector orifice size.
9. Replace the pilot injector. Follow the pilot injector
removal procedure. See table below for injector
orifice size.
Remove the converter cover
from the regulator
CONVERTER
COVER
Pull-out the converter from the
cover
Position of converter when
using
NG
Position of converter when
using
LPG
INJECTOR LOCATION
ORIFICE SIZES
LPG
NG
MAIN BURNER INJECTOR
#52
#37
PILOT INJECTOR
0.2mm
0.4mm
CAUTION: Please replace the corresponding nameplate or label that shows the gas
type operated, after a qualified person converted to another gas type, in order to
prevent injury, death and damage to property.
26