Thor Kitchen TWC2403DI Service Manual Download Page 25

 

 

 

Maintenance Service and Trouble Shooting   

position is to be used for fast freezing or continuous running, its temperature for power 
off is too low, therefore, the compressor won't stop and the temperature in the 
refrigerator becomes lower and lower. 
 
b) Inspection method: check the temperature control knob to see whether it is set in the 
position "coldest". 
 
2) Thermostat is malfunctioning and makes the compressor running continuously 
Analysis of Trouble 
When the thermostat doesn't work normally, it will make the compressor run 
continuously, and hence very low temperature will be achieved in the refrigerator. The 
fault is generally due to the fact that the contacts of the thermostat cannot be released. 
 
Remedy 
Dismantle the thermostat and make a through checkup, if it is totally out of functioning, 
replace it with a new one. 
 
3) Evaporation temperature is too high in refrigerating system, resulting in lower 
refrigerating capacity and hence continuous running of compressor 
 
Analysis of Trouble 
Leakage of refrigerant and clogging in a refrigerating system will directly affect its 
refrigerating capacity. Due to the reduction in its refrigerating capacity, the refrigerator 
temperature cannot reach its rated value, the thermostat won't work, thus the 
compressor runs continuously. When the evaporation temperature in the system is too 
high, the temperature sensing agent in the temperature sensor is also hotter, therefore, 
the thermostat is unable to cut off the power supply to the compressor and stop it. 
 
Remedy 
If it has been found that the refrigerant in the system is insufficient in quantity, recharge 
it with refrigerant. In case clogging occurs, disassemble the part where it is blocked. If 
the evaporation temperature is too high, settle this problem with an appropriate 
quantity of refrigerant. 
 
4) No stoppage of compressor due to damaged heat-insulation layer inside case body 
and/or door seal 
Analysis of Trouble 
When the heat-insulation layer inside the case body deteriorates or the door seal is not 
closely touches the door frame, the temperature in the refrigerator will rise and makes 
the compressor running continuously. 
 
Remedy 
Check the heat-insulation layer for its damaged parts, repair it to improve its 
heat-insulation property. If the door has deformed or the door seal is not tightly sealed 
against the case body, repair them, respectively. 
 
5) Too much food is placed in the refrigerator, or is placed too densely, resulting in poor 
ventilation or poor conditions for temperature sensing, and hence no stoppage of the 
compressor. 

26 

Summary of Contents for TWC2403DI

Page 1: ...Wine Cooler Service Manual Models TWC2403DI Features Energy efficiency Micro foam technology Low noise operation Thick insulation for enerqv efficiency Version number 00 00 Edition 2019 5 20...

Page 2: ...1 CONTENT 1 Content 2 2 Specifications 3 3 Safety precautions 4 4 Function Schedule 7 5 System Flow Chart 8 6 Circuit Diagram 9 7 Maintenance Service and Trouble Shooting 10 8 List of Parts 28 2...

Page 3: ...Color Black Power Supply V Hz 110 60 Rated Input Power W 370 Power Consumption kW h 24h 1 3 Net Weight Lbs 264 Gross Weight Lbs 286 Unit Dimension 60 68 5 187 W D H CM Packing Dimension W D H CM 66 7...

Page 4: ......

Page 5: ......

Page 6: ......

Page 7: ...Function Page Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency 7...

Page 8: ...low Chart 2 Brief Description of System Flow Chart Model TWC2403DI is a fan cooling double system wine cooler When the wine cooler is just powered on the refrigerant flows in the sequence Compressor C...

Page 9: ...n of Control Principle Model TWC2403DI is the direct cooling double system Wine Cooler an electronic type of all the control is generally adopted The display control PCB directly controls the start an...

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ...refrigerator This is a normal sound produced by the pull in or release of the armature of a current deadweight start relay when starting the compressor The compressor motor will produce a slight and...

Page 14: ...ious welding points for leaks if leakage occurs an oil stain can be seen definitely b Check the suction and exhaust pressure values high pressure and low pressure of compressor to see whether they are...

Page 15: ...er the compressor has operated normally for 5 10 minutes Touch and feel the condenser the temperature of its upper part should be higher than that of its lower part or its right part is hotter than it...

Page 16: ...outlet of the capillary and no frost or a smaller quantity of loose frost appears on the evaporator After shut down the balance pressure in the system is usually lower than the saturation pressure cor...

Page 17: ...utes open the tubing evacuate it and then recharge the system with refrigerant 4 Low efficiency of compressor Analysis of Trouble Low efficiency of a refrigerating compressor refers to the actual redu...

Page 18: ...left in the evaporator Dismantle the evaporator purge it thoroughly and then dry it In case it is difficult to dismantle it charge refrigerant from the evaporator inlet to wash it several times then p...

Page 19: ...gerating system has been performed improperly the effect of air purging for the whole system is not good or the water content in the refrigerant is out of standard all these will cause the expansion v...

Page 20: ...s been used for a longer time or by the dirt accumulated gradually inside the filter Sometimes tapping the filter nay cause a passage for flowing touching it with your hand you will feel that it is co...

Page 21: ...rouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure higher discharged gas t...

Page 22: ...w one 3 Sudden stoppage due to other causes Normal Stoppage Start and stop of the compressor is generally controlled by a thermostat When the temperature in the refrigerator reaches its desired value...

Page 23: ...re sensor Remedy Remove the relay cover to check up its contacts if they are open this means that the original setting is not properly set or temperature sensing agent has leaked out of the temperatur...

Page 24: ...upply Dirt and other impurities in the lubricant oil will increase its viscosity and cause the shaft to be seized Copper plating may also result in seizing of shaft b Seizing of piston This is caused...

Page 25: ...temperature cannot reach its rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in th...

Page 26: ...handle or other metal parts with your hand Test the refrigerator with a test pencil it will light up intensively measure the resistance between the power cord plug and the case body with an avometer...

Page 27: ...ecomes weaker or vanishes If the refrigerator has not been levelly placed put a level meter on its top table and adjust the leveling screws on its legs In case noise occurs from the compressor strike...

Reviews: