Maintenance Service and Trouble Shooting

 

Analysis of Trouble 
Leak points in the refrigerating system have not been found and repaired timely. thus 
resulting in the total escape of refrigerant .There are two kinds of leakage : 
 
l) 

Slow leakage 

For instance, when we want to use a refrigerator that has been put out of quite a long 
time, we find the leakage of refrigerant ,or in the course of its operation ,we have found 
that the refrigerator is gradually becoming not so cold and finally no refrigerating cab be 
achieved ; 
 
ii) 

Fast leakage   

In that case .all the refrigerant will escape swiftly due to abrupt rupture of system tubing. 
Symptoms of total leakage of refrigerant are mainly as follows: the compressor can be 
started easily (if there is no damage to the compressor parts) and its operating current 
becomes low .its gas suction pressure is high and discharge pressure is lower .the gas 
discharge tube feels rather cold, no sound of gas eruption from the liquid in the 
evaporator can be heard, and no will gush out of the process tube if you cut it open 
after shutdown . 
 
Remedy 
Check the whole machine, particularly those locations which are liable to leak .After 
leak points have been found ,repair them or replace them with new parts according to 
specific circumstances .then evacuate the system and finally charge refrigerant. 
 
2) Refrigerating system has been clogged 
a)  Clogged with Ice   
Analysis of Trouble 
The dryness treatment for the major parts in the refrigerating system has been 
performed improperly, the effect of air purging for the whole system is not good, or the 
water content in the refrigerant is out of standard, all these will cause the expansion 
valve to be clogged with ice The symptom for this trouble are as follows: the 
refrigerator sometimes can refrigerate and sometimes cannot :the refrigerator 
compartment works normally at the beginning ,but after working for a certain period of 
time ,frosting begins at the clogged position .evaporation temperature reaches below 
0

D

C, water will accumulate at the narrow part of the capillary and clog it gradually .then 

frost begins to melt at the evaporator ,no gas flowing sound can be heard .and the gas 
suction pressure assumes a state of vacuum .Note that these phenomena will appear 
intermittently ; sometimes .the refrigerator works well .and sometimes not well .In order 
to determine whether it is clogged with ice .heat the suspicious points with hot water to 
make ice melt .and after a while if a gas flowing sound resulting from an abrupt gush is 
heard and the gas suction pressure rises as well ,it can be confirmed that the trouble is 
caused by ice clogging . 
 
Remedy 
If there is too much moisture in the refrigerating system, it is advisable to release the 
refrigerant, purge the tubing with nitrogen, and then charge the system with the filtered 
refrigerant. However, the commonly adopted method is to connect a filter with moisture 
absorbers (such as silica-gel, anhydrous calcium chloride) to the refrigerating system 
so as to filter out the moisture from the system, then replace the filter, evacuate it again 
and finally charge the system with refrigerant. 

 

20 

Summary of Contents for TWC2403DI

Page 1: ...Wine Cooler Service Manual Models TWC2403DI Features Energy efficiency Micro foam technology Low noise operation Thick insulation for enerqv efficiency Version number 00 00 Edition 2019 5 20...

Page 2: ...1 CONTENT 1 Content 2 2 Specifications 3 3 Safety precautions 4 4 Function Schedule 7 5 System Flow Chart 8 6 Circuit Diagram 9 7 Maintenance Service and Trouble Shooting 10 8 List of Parts 28 2...

Page 3: ...Color Black Power Supply V Hz 110 60 Rated Input Power W 370 Power Consumption kW h 24h 1 3 Net Weight Lbs 264 Gross Weight Lbs 286 Unit Dimension 60 68 5 187 W D H CM Packing Dimension W D H CM 66 7...

Page 4: ......

Page 5: ......

Page 6: ......

Page 7: ...Function Page Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency 7...

Page 8: ...low Chart 2 Brief Description of System Flow Chart Model TWC2403DI is a fan cooling double system wine cooler When the wine cooler is just powered on the refrigerant flows in the sequence Compressor C...

Page 9: ...n of Control Principle Model TWC2403DI is the direct cooling double system Wine Cooler an electronic type of all the control is generally adopted The display control PCB directly controls the start an...

Page 10: ......

Page 11: ......

Page 12: ......

Page 13: ...refrigerator This is a normal sound produced by the pull in or release of the armature of a current deadweight start relay when starting the compressor The compressor motor will produce a slight and...

Page 14: ...ious welding points for leaks if leakage occurs an oil stain can be seen definitely b Check the suction and exhaust pressure values high pressure and low pressure of compressor to see whether they are...

Page 15: ...er the compressor has operated normally for 5 10 minutes Touch and feel the condenser the temperature of its upper part should be higher than that of its lower part or its right part is hotter than it...

Page 16: ...outlet of the capillary and no frost or a smaller quantity of loose frost appears on the evaporator After shut down the balance pressure in the system is usually lower than the saturation pressure cor...

Page 17: ...utes open the tubing evacuate it and then recharge the system with refrigerant 4 Low efficiency of compressor Analysis of Trouble Low efficiency of a refrigerating compressor refers to the actual redu...

Page 18: ...left in the evaporator Dismantle the evaporator purge it thoroughly and then dry it In case it is difficult to dismantle it charge refrigerant from the evaporator inlet to wash it several times then p...

Page 19: ...gerating system has been performed improperly the effect of air purging for the whole system is not good or the water content in the refrigerant is out of standard all these will cause the expansion v...

Page 20: ...s been used for a longer time or by the dirt accumulated gradually inside the filter Sometimes tapping the filter nay cause a passage for flowing touching it with your hand you will feel that it is co...

Page 21: ...rouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure higher discharged gas t...

Page 22: ...w one 3 Sudden stoppage due to other causes Normal Stoppage Start and stop of the compressor is generally controlled by a thermostat When the temperature in the refrigerator reaches its desired value...

Page 23: ...re sensor Remedy Remove the relay cover to check up its contacts if they are open this means that the original setting is not properly set or temperature sensing agent has leaked out of the temperatur...

Page 24: ...upply Dirt and other impurities in the lubricant oil will increase its viscosity and cause the shaft to be seized Copper plating may also result in seizing of shaft b Seizing of piston This is caused...

Page 25: ...temperature cannot reach its rated value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in th...

Page 26: ...handle or other metal parts with your hand Test the refrigerator with a test pencil it will light up intensively measure the resistance between the power cord plug and the case body with an avometer...

Page 27: ...ecomes weaker or vanishes If the refrigerator has not been levelly placed put a level meter on its top table and adjust the leveling screws on its legs In case noise occurs from the compressor strike...

Reviews: