TS 840 TRANSFER SWITCH
PM057 REV 8 10/01/25
3
Thomson Technology
3.2.
TRANSFER SWITCHES WITH INTEGRAL OVER CURRENT PROTECTION
For models of transfer switch with integral over current protection, the over current
protection must be set prior to operation. The equipment will be shipped from the factory
with a long-time current setting of 100% (of the equipment rating) and maximum short-
time/instantaneous current and time delay settings.
WARNING!
Do Not Energize this equipment until
device settings have been verified to
ensure proper system protection &
coordination. Failure to do so may
result in equipment failure.
Refer to
Section 5.2.2
of this manual for additional information on operation of the Transfer
switch following an over current trip condition.
Refer to information supplied with the transfer switch documentation package for
adjustment procedures on the power switching units over current protection trip unit.
Contact the factory if any additional information is required.