TYPICAL AUTOMATIC TRANSFER SWITCH
COMMISSIONING PROCEDURES
Model Series TS 840
9087A - 198
th
Street, Langley, B.C. Canada V1M 3B1
•
Telephone (604) 888-0110
•
Telefax (604) 888-3370
Note
: The following commissioning procedures are provided for general
information only pertaining to typical site installations and applications.
Contact the equipment supplier for further information as may be required.
DANGER!!!!
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death
CAUTION
Commissioning procedures must be performed by qualified personnel only.
Ensure the Automatic Transfer Switch (ATS) Control Isolation Plug is
disconnected prior to energizing the supply sources. Manually place the transfer
switch mechanism in the neutral position by inserting the manual operating
handle into the mechanism and turning until the neutral postion has been reached
as is indicated on the transfer mechanism.
NOTE: An optional hand held, plug-in Service Display Module (SDM) is available
for the TSC 80 Transfer Controller. The SDM module provides an LCD screen to
display additional detailed information on the operation and settings of the TSC
80 controller for simplified servicing/trouble shooting procedures. For detailed
information, refer to the separate SDM module instruction manual (PM065).
Pre-Commissioning Checks Prior to Commissioning Agent On-Site (to
allow loads to be supplied prior to final commissioning)
1) Verify the system voltage of both sources (i.e. generator and utility) to be applied
to the transfer switch are of the correct nominal system value which matches the
ATS drawings and the ATS equipment label ratings. If system voltage is incorrect
for the rating of the ATS supplied contact Thomson Technology.
CAUTION
:
FAILURE TO RE-CONFIGURE ATS VOLTAGE TO MATCH SYSTEM
VOLTAGE WILL RESULT IN EQUIPMENT MALFUNCTION AND DAMAGE.
2) For 240V High Leg Delta systems refer to the ATS instruction manual for correct
phasing required and re-configuring procedures.