![THOMSON EAP 110 Installation & Operating Instructions Manual Download Page 20](http://html1.mh-extra.com/html/thomson/eap-110/eap-110_installation-and-operating-instructions-manual_1108978020.webp)
EAP 110 ANNUNCIATOR
6. SPECIFICATIONS
SUPPLY VOLTAGE
12V or 24V nominal (+- 20%), negative ground
SUPPLY CURRENT
100 ma (maximum), (+- 20%)
COMMUNICATION PORT
RS 422, 4.8 KBaud, Thomson Technology T-Net Protocol
to MEC 2/MEC 20
8 conductor #22 AWG (min) Shielded/Twisted cable (1000 ft Max),
Plug-in RJ45 Connector
EXTERNAL CONTACT INPUT
Close to DC Negative
TEMPERATURE RANGE
-40 C to +50 Deg C
ENVIRONMENTAL
Faceplate NEMA 12, Rear Enclosure NEMA 1
DIMENSIONS
6.0” W x 6.0” H x 3.0” D (Flush mount adapter option
(7.0” w x 7.0” H)
MOUNTING
Surface Mount (Standard), Flush-mount (Optional)
Rear Enclosure conduit box c/w Qty 8 ½” knockouts
Specifications subject to change without notice.
PM058 Rev 2 06/01/18
Thomson Technology