![THOMSON EAP 110 Installation & Operating Instructions Manual Download Page 16](http://html1.mh-extra.com/html/thomson/eap-110/eap-110_installation-and-operating-instructions-manual_1108978016.webp)
EAP 110 ANNUNCIATOR
DATE
06/01/24
Pow er O n
Com m unication Fail
Progr. #6
Spare
(External Input #1)
Spare
(External Input #2)
Group 2 Alarm Addressing (MEC 2)
Spare
(External Input #3)
Spare
(External Input #4)
EAP 110 Annunciator
Lam p
T est
Alarm
Silence
Under
Voltage
Shutdown
Under
Frequency
Shutdown
Over
Voltage
Shutdown
Over
Frequency
Shutdown
Over
Current
Alarm
High Engine
Tem perature
Shutdown
Low Oil
Pressure
Shutdown
G :\E N GIN EER \PR O D UC T S\EA P110\E AP110 LEXAN GR O UP 2 MEC 2..VS D
FIGURE #8
3.2.3.2. JP3
Low Oil Pressure & High Engine Temp
Shutdown Fault Addressing (Group 1 Addressing):
Fault LED lights D19 & D20 as shown in FIGURE #8 may be
programmed for input from either two different alarm address inputs
when the annunciator is set for group 1 addressing.
With JP3 jumper ON, the EAP 110 Fault LED lights D19 & D20 will be
addressed to external input contacts #4 & #3 as connected to the EAP
110 terminal blocks.
With JP3 jumper OFF, the EAP 110 Fault LED lights D19 & D20 will be
addressed to the MEC 2 or MEC 20 Engine controller Analog Shutdown
circuits for Low Oil Pressure (LOP2) & High Engine Temperature
(HET2) respectively as programmed. If these faults are not
programmed on the MEC Engine Controllers, these fault LEDs will not
be active. Refer to the applicable engine controller instruction manual
for further information.
PM058 Rev 2 06/01/18