background image

Twist

Lubricate

Align

Probe

Wrench Hole

Wrench

IS---0359

March 2010

Page 3 of 4

STEP 3

ELBOW ASSEMBLY

A. Lubricate the cable insulation and inside the elbow

housing with the lubricant supplied. DO NOT

SUBSTITUTE. Other lubricants may be harmful to this

product or its mating product(s). Keep insulation

clean of dirt and grime.

B. Slide the elbow connector onto the cable with a back

and forth twisting motion. Wipe off all excess grease.

C. Align elbow with compression lug’s threaded hole.

D. Thread probe into lug by hand, taking care not to

cross---thread.

The probe

must

turn freely for

approximately four turns before becoming snug.

Tighten with wrench until wrench bends.

STEP 4

CONCENTRIC NEUTRAL CONNECTION

A.

Using a separate copper wire (No. 14 AWG / 2.5mm) or

equivalent, insert one end through the grounding eye

on the elbow. Twist tight taking care not to damage the

eye.

B. Twist all neutral wires and connect to ground using

appropriate connector. Provide adequate slack in

wires for elbow operation.

Grounding

Eye

Provide Slack

for Operation

STEP 5

CONNECT ELBOW AND BUSHING PLUG

A. Lubricate the receptacle portion of the elbow connector and the mating bushing with the lubricant supplied. LUBRICATE

ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE---ENERGIZED.

B. Operate per following instructions.

DO NOT OPERATE BY HAND.

Lubricate only if known to be de---energized

Hotstick

Reviews: