3.6 External battery connection (for extend model only)

1)

Make sure battery quantity complies with the specs (16/18/20 pieces of 12V battery in parallel).
Measure the voltage of battery bank after finishing connection and the battery voltage should be
around 192/216/240Vdc.

NOTICE

1. Don’t mix batteries with different capacity, manufacturers and don’t mix brand new and old

batteries, either.

2. The standard setting of the battery is 16 pcs and battery capacity is 65AH (charge current is

6A).When connecting with 18 pcs or 20 pcs battery, please start up the UPS under AC mode,
connect to the computer to set up battery number and capacity, the UPS will follow battery
capacity to distribute charge current automatically (Max charge current is 6A)

2)

The breaker on battery cabinet should be off.

3)

Remove the cover of terminals. Pay attention! DC voltage is always present on the battery terminals of
UPS.

4)

Connect batteries following this procedure step by step (don’t reverse battery connection):

A) positive pole UPS side to positive pole Battery Cabinet side (BAT+)

B) common pole UPS side to common pole Battery Cabinet side (BAT N)

C) negative pole UPS side to negative pole Battery Cabinet side (BAT-)

Fig.3-4 External battery connection 

YOUR CONNECTION TO SAFETY

Thiele KG 

• V
orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

Thiele KG 

• V

orderer W

einberg 26 • D-71522 Backnang • T

el.: +49 (0)7191 3560-0 

• Fax.: +49 (0)7191 3560-19 

[email protected] 

• www

.thiele-kg.de

YOUR CONNECTION TO SAFETY

klick to

www

u-s-v

YOUR CONNECTION TO SAFETY

klick to

www

ACDC-DCDC

YOUR CONNECTION TO SAFETY

klick to

www

SYSTEME

YOUR CONNECTION TO SAFETY

klick to

www

CONTACT

YOUR CONNECTION TO SAFETY

klick to

www

CALLBACK

Summary of Contents for Mission 10K Series

Page 1: ...www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de YOUR CONNECTION TO SAFETY klick to www u s v YOUR CONNEC...

Page 2: ...24 5 1 Battery maintenance 24 6 Troubleshooting and performance of the product 25 6 1 Troubleshooting 25 6 2 EMC standard Safety standard 25 6 3 Product Performance 26 7 RS232 Communication port defi...

Page 3: ...e electric shock or fire So don t place the containers equipped with liquid on the top of the UPS so as not to cause danger of electric shock and so on 4 Don t put the UPS in a place with high tempera...

Page 4: ...Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26...

Page 5: ...522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de www thiele kg de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0 Fax 49 0 7191 3560 19 info thiele kg de...

Page 6: ...kup unit provides 6A Max 7 Battery Sealed Lead Acid Battery 8 Output filter Complete filtering the output of the UPS to provide the clean power for loads 2 3 Product Category UPS Type Remark Standard...

Page 7: ...cut off the power when in emergency situation PDU is required to connect to the UPS output so as to weaken the affect between loads In order to fix the UPS please lock its wheels by shifting the sheet...

Page 8: ...anel and keep it for further use B Insert the SNMP card and tighten the screws C Connect the UPS with internet by network cable D Refer to the SNMP manual provided to do SNMP setting CAUTION Connector...

Page 9: ...tted with PC through USB See the steps as below 1 Start up the UPS one by one connect USB to the computer start up software and manual are included in the CD ROM 2 Open the set up interface to set up...

Page 10: ...r on battery cabinet should be off 3 Remove the cover of terminals Pay attention DC voltage is always present on the battery terminals of UPS 4 Connect batteries following this procedure step by step...

Page 11: ...ed connecting to UPS to avoid damage Plug UPS on the special socket with over current protection the power socket that used should be connected with ground wire UPS is likely to have output voltage no...

Page 12: ...old the OFF key for 2 seconds to turn off the inverter the UPS is in Bypass mode now b To shut down turn off the UPS completely you need to open the input switch 2 Turn off the UPS with connecting bat...

Page 13: ...ature and ambient temperature 07 CODE Alarm Code Warming Message 08 Software version model DSP version of inverter software model 09 Bus voltage Bus voltage 10 CODE Operational Status and Mode YOUR CO...

Page 14: ...Output voltage 6 Load 7 PFC Ambient temperature up only shows the high temperature Internal temperature down 20 load per grid YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang...

Page 15: ...rmal behaviour s occur s The display value of the above parameter will update within 0 2s Charging status YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 7191 3560 0...

Page 16: ...ncy quantity setting 4 3 2 Output voltage class setting Input Output voltage setting Note Inside the broken line is the flashing part When under the mode setting press On or when under frequency setti...

Page 17: ...der the frequency setting press On or when under battery quantity setting press Off it goes to the battery capacity setting The battery capacity line flashes as in above picture Use button Enter3 to c...

Page 18: ...der bypass voltage lower setting press Off it goes to the bypass upper limit setting The bypass upper limit line flashes as in above picture Use button Enter3 to set the different bypass voltage upper...

Page 19: ...r the parallel ID setting can enter the buzzer setting Now the setting status is flashing as the Figure 14 shows note on mute off no mute When press it shows the mute cycle setting the selection inclu...

Page 20: ...Self test Time is 10 seconds When choosing On2 UPS can transfer to Battery Mode automatically per 30 days And the Battery Self test Time is 10 minutes YOUR CONNECTION TO SAFETY Thiele KG Vorderer Wein...

Page 21: ...setting and goes to bypass lower limit setting or parallel quantity setting NOTICE Parallel cable cannot be connected when setting the parallel parameters 4 3 11 Parallel quantity setting Parallel qua...

Page 22: ...n it goes to the parallel redundancy quantity setting The parallel redundancy quantity flashes as in above picture Use button Enter3 to set the parallel redundancy quantity The parallel redundancy qua...

Page 23: ...Thyristor broken Beep continuously Fault LED lit 7 Fuse broken Beep continuously Fault LED lit 8 Parallel relay fault Beep continuously Fault LED lit 9 Fan fault Beep continuously Fault LED lit 10 Re...

Page 24: ...S turned on please connect load one by one It is recommended that the generator capacity is as twice as UPS rated capacity 5 MAINTENANCE UPS use in the appropriate environment see 3 2 installation not...

Page 25: ...y charged Keep UPS connecting with mains power for more than 8 hours recharge battery UPS overload Check the usage of loads remove some redundant devices Battery aged When replace battery contact fran...

Page 26: ...ncy track speed 1Hz s stand alone 0 5Hz s parallel operation Load capacity Mains drop a level in battery mode 105 110 lasts 1 hour 110 125 lasts 10 minutes 125 150 lasts 1 minute 150 switch to bypass...

Page 27: ...h mm 250 Depth mm 502 Net weight Kg 62 64 Color Black Box content TYPE MISSION 6KVA MISSION 10KVA User Manual Software CD ROM RS232 Cable 1 USB Cable 1 EPO Connector 1 Note 16 pcs 7 9Ah Battery can be...

Page 28: ...off on setting RS 232 communication data format Baud rate 2400bps Byte length 8bit End bit 1bit Parity check none YOUR CONNECTION TO SAFETY Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 49 0 719...

Reviews: