Important information and warnings!

Plumbing connections

The unit is a closed outlet water heater and is intended to operate at the pressure of the water mains, where the flow 
of water is controlled by one or more taps or valves in the outlet line.

The unit can be installed into any type of commercial or residential construction as per the current local Plumbing 
Standards.

It is mandatory for a water pressure limiting valve and a shutoff valve to be connected in series 
with the unit‘s cold water inlet connection.

•  The maximum rated operating line pressure is 1 MPA / 10 bar / 145 PSI.
•  The minimum operating pressure is atmospheric pressure. 
•  The installation of a pressure limiting valve (a mandatory requirement) ensures that excess water pressure applied, 

as result of water hammer and/or other circumstances, does not stress the appliance unduly.

•  The in-line water pressure limiting valve must be rated at 5.0 BAR / 72.5 PSI / 500 KPA.
•  The shutoff valve installed must not be a non-return valve.
•  If the water heater is supplying a dishwasher or washing machine, a water hammer arrestor must be installed on 

the outlet side of the water heater.

Water inlet and outlet connections

The inlet and outlet water connections are both ½” 
BSP SERIES GB.  There are three options for inlet/outlet 
connections with this unit:

Single unit installation

Tandem unit installation

1. Braided hose with seal

3. Braided hose without seal

2. Straight copper tube

ThermoSphere nor its Distributors will be liable for any damages caused by failure to comply with the installation and operating 

instructions outlined in this manual – specifically in this instance where the specified water pressure limiting valve and shutoff 

valve type, as indicated, must be installed with this unit. If the unit is supplying a dishwasher or washing machine a water 

hammer arrestor must be installed at the outlet side of the unit, failure to do so will void warranty.

TSMEB

Outlet

Hot water

out

Cold

water in

Shutoff

valve

Pressure limiting 

valve (5 BAR)

Inlet

TSMEB

Outlet

TSMEB

Stage 1 heated 

water

Max 250mm

Stage 2 hot

water out

Cold

water in

Shutoff

valve

Pressure limiting 

valve (5 BAR)

Inlet

Summary of Contents for TSMEB-10

Page 1: ...HEATING WATER MICRO ELECTRIC BOILER Live well INSTALL GUIDE...

Page 2: ...f your work Just scan the QR code or search online for ThermoSphere CONNECT and fill in the form Nice and easy After you sign up instantly start uploading your receipts to gain your rewards Join in 60...

Page 3: ...Installation options 8 Specifications 9 Flow rates 10 Installation procedure 11 Mounting to the wall 12 Electrical terminals and connections 13 Wiring diagrams for single and tandem installations 14 P...

Page 4: ...ThermoSphere Bridge House Pattenden Lane Marden Kent TN12 9QJ United Kingdom hello thermosphere com 0800 0195899 2 The process will then follow the ThermoSphere Product Warranty Flow Chart to assess w...

Page 5: ...eferably be installed in a vertical position on an internal wall or in an internal cupboard or space If the safety rules or the instructions outlined in this manual are not followed correctly the unit...

Page 6: ...g 2 TSMEB Top Cover 13 TSMEB Inlet Filter 3 TSMEB Heat Sink 14 PCB Terminal Block 4 TSMEB Flow Rate Sensor 15 Electric Mains Supply Cable Gland 5 TSMEB Temperature Sensor Receptacle Cable and Plug Ass...

Page 7: ...s or improper use voids the warranty Never remove the unit cover unless the electricity is turned off at the isolation switch or switchboard To reduce the risk of electric shock or injury to persons o...

Page 8: ...ls and labour It also eliminates wasted water and wasted energy by delivering water at the correct temperature within seconds Point of use with cold feeds or mixer taps TSMEBs can be installed to supp...

Page 9: ...d inside only Ambient temperatures 5 C Drain unit if the ambient temperature is likely to drop below 5 C Standards CE Warranty 3 years Electrical specifications Model TSMEB 5 TSMEB 6 TSMEB 7 TSMEB 8 T...

Page 10: ...11 4 6 9 13 8 8 16 9 2 17 25 C 2 8 5 6 3 4 6 8 4 1 8 2 4 8 9 6 5 5 11 35 C 2 4 2 5 5 2 9 5 8 3 4 6 8 3 9 7 8 45 C 1 5 3 1 9 3 8 2 3 4 6 2 7 5 4 3 1 6 2 Flow rates and energy use with input water at 5...

Page 11: ...supplying the 240VAC electrical mains to the TSMEB are turned OFF 7 Carefully replace the plug and cable connecting the display PCB LED indicator to the PCBA 8 Connect a water pressure limiting valve...

Page 12: ...d the mains supply cable gland fitting hole must not be drilled out Any holes drilled within these areas the sides of the unit or opening out the cable gland fitting hole will render the unit inoperab...

Page 13: ...o thermosphere com 13 Electrical terminals and connections 1 2 3 4 5 6 Electric supply cable gland Printed circuit board assembly PCBA Terminal block Display PCB PCBA reset button Display PCB plug and...

Page 14: ...cause an earth leakage detection Error code FC With tandem installations both units must be fitted with their own respective RCBO and an isolation switch in line with the xed wiring to each electrica...

Page 15: ...talled must not be a non return valve If the water heater is supplying a dishwasher or washing machine a water hammer arrestor must be installed on the outlet side of the water heater Water inlet and...

Page 16: ...dy for use Step 1 Flush Flushing is required to clear the unit of plumbing debris that may have collected in the piping during installation This is done with the electric power supply turned off Flush...

Page 17: ...slow or fast flashing GREEN Fast flashing GREEN Unit is operating and water is being heated Flashing RED continuously Irresolvable error and mechanical lockout Unit will no longer operate until the e...

Page 18: ...mal operation No error 01 Fast flashing GREEN Heating normal operation No error N A Solid ORANGE Water conductivity too low No error N A Solid ORANGE In priming mode No error A4 Flashing RED Operating...

Page 19: ...D indicators on the PCB will be illuminated when the unit is in standby running or in error mode 2 Press the PCBA reset button If the RED LED remains either flashing or illuminated and error condition...

Page 20: ...ps showers supplied Incoming water temp C Set water temp C System flushed and primed Single or Tandem install The stock no of the product You can find this on the label under the unit The serial no of...

Page 21: ...0800 019 5899 hello thermosphere com 21 Notes...

Page 22: ...0800 019 5899 hello thermosphere com 22 Notes...

Page 23: ...23 135mm 285mm Installation hole marking template 170mm...

Page 24: ...Thermogroup Ltd Bridge House Pattenden Lane Marden TN12 9QJ E OE Thermogroup Ltd 2022 0800 019 5899 hello thermosphere com www thermosphere com TSMEBIG_1121_v1 2 Live well...