Factory settings for the 3 fan speeds are shown in Table 5 below:
(refer also to wiring diagrams in Appendix 2)
Fan Speed
Maximum air
velocity at
outlet grille
(m/s)
Maximum air curtain
mounting height
(m)
Sound Pressure
Level of air
curtain
[dB(A) at 3m]
Air Volume
Flow Rate
(m
3
/h)
[for E & A]
HIGH
(black wire)
11.0 4.0
PHV1000 - 59
PHV1500 - 60
PHV2000 - 61
2880
4020
5760
MEDIUM
(blue wire)
–
–
PHV1000 - 57
PHV1500 - 57
PHV2000 - 59
2585
3815
5170
LOW
(red wire)
–
–
PHV1000 - 56
PHV1500 - 53
PHV2000 - 58
2420
3690
4840
Sound pressure levels dB(A) at 3m distance are for a single air curtain mounted at its maximum mounting height, operating in
a room with average acoustic characteristics as defined in CIBSE Guide B5 (reverberation time 0.7s at 1kHz) and a room size
equivalent to 8 air changes per hour (ac/h). Care needs to be taken when selecting air curtains for an installation as noise
levels can be several dB higher if the mounting height is reduced, if the room is more ‘live’ (i.e. hard surfaces, no furnishings or
absorbent materials), if the room is smaller than 8 ac/h equivalent or a combination of these factors. Noise levels will also
increase if more than one air curtain is installed at the same doorway (e.g. +3dB(A) for 2 equal point sources: direct field).
15.1 Remote Control Switch
(for Ambient units)
1 On/Off
Turns the air curtain fans On or Off.
2, 3 & 4 Fan speed
Switch fan speed between Low, Medium and High respectively.
14. FAN SPEED SELECTION
15. REMOTE CONTROL OPERATION
1
2
4
3
Table 5