Installation, use and maintenance guide
BOSKY 30/F30 EVO
– BOSKY COUNTRY 30/F30 EVO
6.3 INSTALLATION OF THE CIRCULATING PUMP ON BOSKY 30/F30 EVO
It is mandatory to connect the circulating pump (not supplied as standard) to the dedicated terminal block.
The terminal block is located behind the LH side panel. Therefore you will have to remove it in order to reach the terminal block.
Connect the power supply (230 V) to the terminals as indicated in the figure below. Then connect the circulating pump to the
terminals (PUMP). The circulating pump will thus activate as soon as the water in the boiler will exceed the temperature of about
60°C.
This operation must be exclusively performed by qualified professional staff, as set forth by Decree no. 37 of 22nd
January 2008 and applicable laws on the subject. Before performing said task, make sure the power supply cable is
disconnected from the electrical power socket.
KEY
KEY
PUMP
PUMP
ANTICONDENSATION
ANTICONDENSATION
CIRCULATING PUMP
CIRCULATING PUMP
ATTENTION: it is mandatory to earth the generator. If this instruction is not observed serious damage, which
is not covered by warranty, will result to the body of the generator. Have an electrician check the earthing.
There must be no electric potential (Volt) between the earth of the generator and the actual earth of the
system. To prevent electrochemical corrosion of the boiler body do not use galvanised pipes and fittings.
Dedicated ground wires must be used to ground all other materials.
6.4 INSTALLATION OF THE CIRCULATING PUMP ON BOSKY COUNTRY 30/F30 EVO
It is mandatory to connect the circulating pump (not supplied as standard) to the dedicated terminal block.
The terminal block is located behind the LH side panel. Therefore you will have to remove it in order to reach the terminal block.
Connect the power supply (230 V) to the terminals as indicated in the figure below. Then connect the circulating pump to the
terminals (PUMP). The circulating pump will thus activate as soon as the water in the boiler will exceed the temperature of about
60°C.
This operation must be exclusively performed by qualified professional staff, as set forth by Decree no. 37 of 22nd
January 2008 and applicable laws on the subject. Before performing said task, make sure the power supply cable is
disconnected from the electrical power socket.
Summary of Contents for Bosky 30 EVO
Page 2: ...Page 1 Installation use and maintenance guide BOSKY 30 F30 EVO BOSKY COUNTRY 30 F30 EVO ...
Page 38: ...Page 37 Installation use and maintenance guide BOSKY 30 F30 EVO BOSKY COUNTRY 30 F30 EVO ...
Page 40: ...Page 39 Installation use and maintenance guide BOSKY 30 F30 EVO BOSKY COUNTRY 30 F30 EVO ...
Page 42: ...Page 41 Installation use and maintenance guide BOSKY 30 F30 EVO BOSKY COUNTRY 30 F30 EVO ...