List of alarms/events:
Alarm 01:
Probe PT100
Probe signal lost (sensor or cable).
The heating control is instantly disabled.
Alarm 02:
Overheating.
Temperature above 220°C
Temperature reading above 230°C.
The heating control is instantly disabled.
Alarm 06:
Upper pressing sensor not reached
Signal not detected after 5 seconds. Caused by
faulty sensor, lack of compressed air supply,
jamming (mechanical, etc)
Alarm 07:
Lower pressing sensor not reached
Signal not detected after 5 seconds. Caused by
faulty sensor, lack of compressed air supply,
jamming (mechanical, etc)
Alarm 10:
Communication error
Communication lost between power board
and screen board.
Contact your stockist.
Alarm 13:
Temperature not reached
Blocks first cycle start request. Permits cycle
start at second request (forced start despite
setpoint not being reached).
Press the red/orange area to clear the fault.