Instructions for installation and use of condensing boilers
Therm 17 KD, KDZ, KDZ 5
Page 1: ...Instructions for installation and use of condensing boilers Therm 17 KD KDZ KDZ 5...
Page 2: ...NS FOR OPERATION AND MAINTENANCE 10 BOILER OPERATION 10 7 MODULATING ELECTRONICS DIMS03 TH01 12 8 GAS FITTING SIT 848 SIGMA 15 9 WARRANTY AND RESPONSIBILITY FOR DEFECTS 16 10 GRAPH OF POSSIBLE HEATING...
Page 3: ...LERS THERM 17 KD gas boiler is composed of a carry frame to which all operational components of the boiler are attached Giannoni compact condensing body which conjugates the combustion chamber and bur...
Page 4: ...ored by a flow switch integrated in the multi purpose GRF 3 collector together with the bypass valve for charging the heating system from the service water inlet or potentially from an external connec...
Page 5: ...0 Diameter of the coaxial venting mm 60 100 60 100 60 100 Mean combustion product temperature o C 50 50 50 Combustion product flow by weight natural gas g s 1 2 1 9 8 2 1 9 8 2 1 9 8 Max noisiness acc...
Page 6: ...the ambient temperatures within the range of 5 to 35 C and maximum relative humidity of 80 Objects in the sense of Czech standard SN 06 10 08 classified according to Czech standard SN 73 08 23 must n...
Page 7: ...er expansion vessel capacity it is necessary to install another expansion vessel in the system CONDENSED WATER DRAINAGE The boiler is fitted with a running trap syphon which must be filled with approx...
Page 8: ...luding the outlet distance pieces piping fittings designed for the supplied boiler type These boiler components are supplied separately depending on the type and concrete installation conditions the b...
Page 9: ...re regulation e g Honeywell CM 707 CM 907 or Electrobock PT 21 PT 30 etc An outdoor THERM Q01 sensor is supplied by Thermona for an expedient equitherm regulation An intelligent THERM RC 03 programmab...
Page 10: ...persons over 18 years of age Service buttons are designed for boiler diagnostics and parameter settings Heating temperature setting regulator for user setting of the output temperature of water in the...
Page 11: ...setting is finished the set temperature value will be indicated for the following roughly 5 seconds The actual temperature of the respective operating mode is indicated by the subsequent permanent dis...
Page 12: ...1 HSW DS2 outdoor sensor DS3 cascade DS4 DS5 DS6 OFF tank without the outdoor sensor slave ON flow with the outdoor sensor master Default setting DS1 depends on the boiler type DS2 OFF mode 1 1 DS3 OF...
Page 13: ...n of the equitherm curve displacement in the range of 15 C of the heating water by the heating water temperature regulator on the control panel The equitherm curve is modified for a standard heating s...
Page 14: ...m the combustion chamber Regular pump start up if boiler does not operate for 30 seconds after 24 hours of inactivity Regular contact making of the intercepting valve for 10 seconds after 24 hours of...
Page 15: ...output i e minimum ventilator speed is already set By tightening the screw the amount of gas in the mixture increases 2 Setting the air gas mixture ratio To do this use the regulatory screw of the gas...
Page 16: ...llation of the el voltage chiefly excess voltage peaks gas pressure and purity etc defects of the appliances outside the boiler which affect its function inappropriate venting impurities in the combus...
Page 17: ...ssure of THERM 17 KDZ 17 KDZ 5 0 0 50 0 100 0 150 0 200 0 250 0 300 0 350 0 400 0 450 0 500 0 0 4 0 6 0 8 1 1 2 Water flow m3 h Outlet over pressure mbar Wilo 3 Grunfos 3 Warning The curves of possibl...
Page 18: ...18 11 El diagram of THERM 17 KD connection with the DIMS03 TH01 automatics...
Page 19: ...19 12 El diagram of THERM 17 KDZ KDZ 5 boilers connection with the DIMS03 TH01 automatics...
Page 20: ...40997 Grundfos pump st No 41367 Syphon st No 21059 1 Conjugated fitting GRF 3 st No 26072 Safety valve st No 40302 Ventilator RG130 0800 3612 031111 st No 42195 Mixer AGU3 645 A 109 st No 42197 Blocki...
Page 21: ...ansion vessel st No 22168 Transformator 220V 24V st No 24477 Gas valve SIT st No 40997 Grundfos pump st No 41367 Siphon st No 21059 1 Conjugated fitting GRF 3 st No 26072 Safety valve st No 40302 16 T...
Page 22: ...tor 220V 24V st No 24477 Mixer AGU3 645A109 st No 42197 Ventilator RG130 0800 3612 st No 42195 Safety thermostat st No 40035 Gas valve SIT st No 40997 Three way valve st No 21053 Grundfos pump st No 4...
Page 23: ...71 90 100 80 177 O60 425 800 160 800 1 Recuperative water inlet G 3 4 external thread 2 Heating water outlet 3 Gas inlet G 1 2 external thread 4 Service water inlet G 1 2 external thread 5 Service wat...
Page 24: ...either concentric or located in such small distance within 50cm that it is subject to the same meteorological conditions C43 Separate connection to the two pipes of a common shaft The outlet can be ei...
Page 25: ...ompliant with the requirements specified in Section 10 of the Act No 185 2001 Coll and Section 6 of the Act No 477 2001 Coll The product package is normally disposed of in a scrap paper collecting cen...
Page 26: ...o the EC notified body No 1015 THERM 17 KD THERM 17 KDZ THERM 17 KDZ 5 test certificate of type according to the EC Directive on appliances burning gaseous fuel 90 396 EEC No E 30 00571 07 as of Augus...