Example: The contents of the holding register 1001H are the read out from slave address 1. 
Query message:        01 03 10 01 00 01 D1 0A 
Response message: 01 03 02 

00 FD 

79 C5 

Explain

00FD=253,is processed as 25.3 

 
10.5 Preset single register [06H] 
The query message specifies data to be written into the designated holding register. Only R/W holding 
registers can be specified. The controller EEPROM had a life span of data written to the EEPROM less than 
1000,000 times 

Slave address 

Function code 

Register 
address 

Write data 

CRC16 

Example: Data is written into the holding register 0004H of slave address 1. 
Query message:        01 06 00 04 FF 38 88 29 
Response message: 01 06 00 04 FF 38 88 29 
When input set value(SV) is -20.0,-20.0 is processed as -200,-200=0000H-00C8H=FF38H 

10.6 No response 
The slave ignores the query message and does not respond when: 
• The slave address in the query message does not coincide with any slave address settings. 
• The CRC code of the master does not coincide with that of the slave. 
• Transmission error such as overrun, framing, parity and etc., is found in the query message. 
• The Communication time interval less than 300ms. 
10.7 Register address list: 
Symbol 

Decimal point 

Real Register 

Holding Register 

Measured value(PV) 

YES 

1001H~1004H 

44098~44101 

The first public parameters

 (Refer to 5. Parameters)

 

Lock 

NO 

0000H 

40001 

TS 

NO 

0001H 

40002 

… and so on

 

Baud 

NO 

0009H 

40010 

The Parameters of   channel 1 

(Refer to 5. Parameters)

 

SP1~ COL1 

000AH~0012H 

40011~40019 

The Parameters of   channel 2

 (Refer to 5. Parameters)

 

SP2~ COL2 

0013H~001BH 

40020~40028 

The Parameters of   channel 3

 (Refer to 5. Parameters)

 

SP3~ COL3 

001CH~0024H 

40029~40037 

The Parameters of   channel 4 

(Refer to 5. Parameters)

 

SP4~ COL4 

0025H~002DH 

40038~40046 

 

Character Symbols 

This manual indicates 9-segment display characters as shown below. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for PID-4CH-SSR

Page 1: ... Standard Alarms Can be output an alarm when the deviation process value set point or manipulated value reaches a specified value 1 5 Sampling Time 2 sec 1 6 Use this controller within the following allowable range Allowable ambient temperature 0 to 55 C Allowable ambient humidity 5 to 85 RH 2 Dimensions h w d Unit mm 96 96 112 Panel cutout 92 92 3 Parts Description 1 ALM lamp Lights when Event oc...

Page 2: ...iation low alarm 5 Band alarm 6 Out of band alarm 0 6 0 3 Kt PID control cycle PID control response time ____ 120 4 Dp Decimal point position selection Set the position of the decimal point for the measured value to be displayed 0 1 1 5 P SH Range high Input range 0 6 P SL Range low 9999 7 C F Measured value PV unit select C Celsius F Fahrenheit If the value is changed the controller needs to exec...

Page 3: ...control P 0 Relay contact may repeat its turning ON and OFF due to input fluctuation if measured value PV is near the alarm set value the differential gap setting can prevent the relay contact from ON or OFF repetition 0 1 50 0 1 0 8 AT N Auto tuning 1 AT with learning start 0 AT with learning stop 0 1 0 9 COL N Hot Cold 0 reverse control heating 1 positive control cooling 0 1 0 6 Operation 6 1 Fi...

Page 4: ...splay AT and PV value now meter s control way is on off mode after 3 times vibrating 3 control period automatic save P I D parameter the self adjusting procession finished Operation will be as shown in the following diagram Attentions when Auto tuning the controller should not change the set value When the power off during Auto tuning it will restart Auto tuning next time When it need artificially...

Page 5: ... slave A typical message consists of a request query message sent from the master followed by an answer response message from the slave When master begins data transmission a set of data is sent to the slave in a fixed sequence When it is received the slave decodes it takes the necessary action and returns data to the master 10 1 Communication Mode Data bit length Stop bits Parity bit Communicatio...

Page 6: ...s not respond when The slave address in the query message does not coincide with any slave address settings The CRC code of the master does not coincide with that of the slave Transmission error such as overrun framing parity and etc is found in the query message The Communication time interval less than 300ms 10 7 Register address list Symbol Decimal point Real Register Holding Register Measured ...

Reviews: