5. Parameters
ID
Symbol
Name
Manual
Setting
range
Ex-Factory
The public parameters(First level)
0
LocK
Set data lock
LOCK=18, Set data unlock
LOCK≠18, Set data lock.
0
~
50
18
1
TS
Input type
Cu50; Pt2 (pt100); K; E;J;T; S
-
-
2
ALP
Alarm type
0: Alarm function OFF;
1:Process high alarm;
2:Process low alarm;
3: Deviation High alarm ;
4: Deviation low alarm;
5: Band alarm
6: Out of band alarm.
0-6
0
3
Kt
PID
control cycle.
PID control response time
____
120
4
Dp
Decimal
point
position
selection
Set the position of the decimal point for
the measured value to be displayed.
0-1
1
5
P-SH
Range high
Input range.
0
6
P-SL
Range low
9999
7
C-F
Measured value
(PV) unit select
C: Celsius F: Fahrenheit
If the value is changed, the controller
needs to execute Auto-tuning again. Refer
to 6.Auto-tuning
C , F
C
8
Addr
Address
Communication address can be set from 0
to 255
1
~
255
1