ACU-STEAM HUMIDISTAT, version A
Features
State of Art digital RH sensor
ROOM or DUCT mounting
Reprogrammable Microcontroller
Potentiometer Set-point setting
Out-door temperature sensor for Set-point Reset
Green (ON/OFF) and Red (warning) status LEDs
Specifi cations
Set-point range. . . . . . . . . . . . . . . 20% to 50% Relative Humidity
Accuracy. . . . . . . . . . . . . . . . . . . . ±4.5%, without calibration
Linearity . . . . . . . . . . . . . . . . . . . . ±1% in the Set-point range
Differential % RH. . . . . . . . . . . . . ±2%
Outdoor Temp. Reset Range
between -9 ˚F (-23 ˚C) to 27 ˚F (-3 ˚C)
Outdoor reset Temperature vs. Set point change
28
˚F (-2 ˚C) and warmer
No change
27
˚F (-3 ˚C) to 23 ˚F (-5 ˚C) 42%
max,
22
˚F (-6 ˚C) to 18 ˚F (-8 ˚C) 38%
max,
17
˚F (-9 ˚C) to 12 ˚F (-11 ˚C)
34%
max,
11
˚F (-12 ˚C) to 5 ˚F (-15 ˚C)
30%
max,
4
˚F (-16 ˚C) to -2 ˚F (-19 ˚C)
26%
max,
-3
˚F (-20 ˚C) to -9 ˚F (-23 ˚C)
22%
max,
-9
˚F (-23˚C) and colder
20% max.
NOTE: these ranges can vary by ±2 %.
The Outdoor Temperature sets the maximum set point of RH internally.
If the Dial position is higher, the actual set point will be limited as above.