CONNECTION PLAN 

If the RS485 cable is looped through, connect both cable shields using the enclosed 2-pol. Connect terminal as shown. 

F RS485 Modbus 

 

Looped through power supply, valid from 08/03/2020 (20216) 

 

 

UB+ 

15..35 V = / 19..29 V ~ 

GND 
AOU2 

temperature 2* | 0..10 V 

AOU1 

humidity 1 | 0..10 V 

GND 

15..35 V = / 19..29 V ~ 

UB+ 

 

A+ 

RS485 

A+ 
B- 
B- 

 

 

 0..5 V 

 

 0..10 V 

 

» 

DIP-SWITCH-SETTINGS 

*factory default settings 

Termination 120 Ω

 

 

Modbus adress 

 

 

 

 

 

 

 

Not active* 

active 

ON=2

0

 (1)*

 

ON=2

1

 (2)

 

ON=2

2

 (4)

 

ON=2

3

 (8)

 

ON=2

4

 (16)

 

Baud 

 

 

 

 

 

 

 

 

Sample adress: 26 

 

9600* 

19200 

Parity

 

 

 

 

 

 

 

 

 

 

 

38400 

57600 

none* 

(2-stopbits) 

even 

(1-stopbit) 

odd 

(1-stopbit) 

none 

(1-stopbit) 

 

 
The modbus address of the device is set in the range of 1 ... 31 (binary encoded) using a 5-pole DIP switch. With address 0 via DIP, an extended 

address range (32..247) is available via USEapp. 
 

Address 

Access 

Description 

Resolution / Unit 

relative humidity 

0.1  %rF 

 

Register 400 = 1 (Unit SI) 

Register 400 = 2 (Unit Imperial) 

Address  Access  Description 

 

Resolution / Unit 

 

Resolution / Unit 

Temperature 

 

SI 

0.1 

°C 

 

Imperial 

0.1 

°F 

Absolute humidity 

 

SI 

0.01 

g/m³ 

 

Imperial 

0.01  Gr/ft³ 

Enthalpy 

 

SI 

0.1 

kj/kg 

 

Imperial 

0.1 

BTU/lb 

Dew point 

 

SI 

0.1 

°C 

 

Imperial 

0.1 

°F 

 

 

Modbus addresses: 

USE-RS485 Modbus Interface

 

 

 

A detailed description of the Modbus addresses can be found under the following link: 

→ 

Download

 

 

 

ON

1

3

2

4

5

A+ 

B- 

A+ 

B- 