Issue date: 12.05.2022
Page 3 / 4
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· [email protected]
FT-RDF18+_RS485_Modbus_Datasheet_en.docx © 2022
»
CONNECTION PLAN
If the RS485 cable is looped through, connect both cable shields using the enclosed 2-pol. Connect terminal as shown.
F RS485 Modbus
Looped through power supply, valid from 08/03/2020 (20216)
UB+
15..35 V = / 19..29 V ~
GND
AOU2
temperature 2* | 0..10 V
AOU1
humidity 1 | 0..10 V
GND
15..35 V = / 19..29 V ~
UB+
A+
RS485
A+
B-
B-
0..5 V
0..10 V
»
DIP-SWITCH-SETTINGS
*factory default settings
Termination 120 Ω
Modbus adress
Not active*
active
ON=2
0
(1)*
ON=2
1
(2)
ON=2
2
(4)
ON=2
3
(8)
ON=2
4
(16)
Baud
Sample adress: 26
9600*
19200
Parity
38400
57600
none*
(2-stopbits)
even
(1-stopbit)
odd
(1-stopbit)
none
(1-stopbit)
The modbus address of the device is set in the range of 1 ... 31 (binary encoded) using a 5-pole DIP switch. With address 0 via DIP, an extended
address range (32..247) is available via USEapp.
Address
Access
Description
Resolution / Unit
1
R
relative humidity
0.1 %rF
Register 400 = 1 (Unit SI)
Register 400 = 2 (Unit Imperial)
Address Access Description
Resolution / Unit
Resolution / Unit
0
R
Temperature
SI
0.1
°C
Imperial
0.1
°F
2
R
Absolute humidity
SI
0.01
g/m³
Imperial
0.01 Gr/ft³
3
R
Enthalpy
SI
0.1
kj/kg
Imperial
0.1
BTU/lb
4
R
Dew point
SI
0.1
°C
Imperial
0.1
°F
Modbus addresses:
USE-RS485 Modbus Interface
A detailed description of the Modbus addresses can be found under the following link:
ON
1
3
2
4
5
A+
B-
A+
B-