To connect the room thermostat, remove the
cap.
8.
Install the flue (1 m and a rain cap).
9.
Make sure the convector heater is switched
off. See fig. 7.
10. Check the supply voltage: see identification
plate.
11. Connect the convector heater to the socket of
the electric power supply.
The indicator light “Panel live” is on.
12. If necessary, press the reset switch.
13. Reset the thermostat, see fig. 7.
3.3
Start up
To start up the heating:
1.
Open the fuel cock (B), see fig. 8.
2.
Turn the rotary switch to position 3, 4 or 5,
see fig. 7.
The fan will start up slowly.
The burner always starts up in the LOW
position. When the HIGH position has been
selected, the burner will automatically switch
to the HIGH position.
The convector heater will produce heat after
some minutes. This depends on the outside
temperature.
3.
Set the room thermostat.
The convector heater will produce hot air
after some seconds.
To start up the ventilation:
1.
Turn the rotary switch to position 1 of 2, see
fig. 7.
The fan will start up slowly.
4
USE
4.1
During operation
4.2
Switch off
Switch off heating:
1.
Turn the rotary switch to position “0”.
The magnet valve(s) close(s) and stop(s) the
fuel supply.
The convector heater stops burning.
2.
Shut off the fuel supply.
Switch off the cooling:
1.
Turn the rotary switch to position “0”.
The ventilator will automatically stop.
4.3
Transport after use
1.
Switch off the convector heater and wait until
the fan has stopped completely.
2.
Switch off the power supply.
3.
Remove the connection from the room
thermostat and place the cap on the
thermostat connection.
4.
Remove the air hoses.
5.
Remove the flue.
6.
Remove the fuel connection.
5
MAINTENANCE
5.1
Maintenance table
Use the table in this booklet to record performed
maintenance after each winter season.
/i
Caution
Do not switch on the convector heater if
there is no fuel, or if the connected fuel
tank is empty.
Hot
Do not touch the flue stack or blower
outlet! The flue stack and blower outlet
get hot during operation!
Caution
After switching off the convector heater,
the ventilator will continue to run. The
ventilator will cool down the convector
heater to prevent damage by
overheating. The ventilator will
automatically stop.
The fan can start again without warning.
Description
Period
Yearly
Check the fuel pump for leakage, corrosion and dirt.
User
Check the general condition of the fuel pump, fans, ignition, photocell, burner, electrical
installation and heat exchanger.
Dealer
Check the fuel lines for blockages, corrosion and leakage.
User
Check the fan of the burner for corrosion and dirt.
User
Check the fan for corrosion and dirt.
User
Summary of Contents for IMAC 4000
Page 4: ...4 40 020 949 rev 05 2011 IMAC Nederlands 5 English 14 Deutsch 23 Fran ais 33 Espa ol 42 52...
Page 53: ...IMAC 40 020 949 rev 05 2011 53 1 1 1 1 2 2 A B 1 3 3 A B C D E 1 4 1 5 2 2 1 2...
Page 58: ...58 40 020 949 rev 05 2011 IMAC V 6 6 1 i V 1 2 7 I 3 4 5 6 7 8 9 10 7 G 11 12 13 9...
Page 59: ...IMAC 40 020 949 rev 05 2011 59 14 15 16 17 18 8 19 20 21 22 23 24 9 25 2 26...
Page 62: ...62 40 020 949 rev 05 2011 IMAC 10 E www thermobile nl...
Page 68: ...68 40 020 949 rev 05 2011 IMAC...