PREPARATIONS
3.1
Removing the packaging
1. Remove packaging from the heater.
3.2
Installation
1. Make sure that the heater has a stable
set-up.
2. Hang the heater on the suspension eyes.
3. Fit a gas cock with an internal
screwthread of 1/2” to the gas inlet of the
heater, see fig. 7 (A).
4. Connect the heater to the gas supply.
5. Shut the gas cock off and place the gas
pipe under pressure.
6. Check the burner pressure.
7. To connect an outside-air suction device
to the combustion air fan inlet, see
chapter 9.
8. If the heater is provided with a room
thermostat or time clock, connect it to the
appropriate connection (E) of the
operating panel (fig. 5). As standard, this
connection is provided with a plug to
which the contacts are connected.
9. Insert the plug in the socket.
3.3
Preparing for start-up
1. Check if the heater is correctly adjusted
for the locally-supplied gas (consult the
dealer).
3.4
Starting up
Heat:
1. Open the gas cock.
2. Switch the selector switch (D) to heat,
see fig. 5.
Ventilate:
1. Switch the selector switch (D) to
ventilate, see fig. 5.
4
USE
4.1
During operation
The heater can be positioned both
horizontally and vertically (blowing up
or down).
•
Horizontally: a minimum of 0.5 m
above the floor.
•
Vertically blowing down: a
minimum of 1.4 m above the
floor.
•
Vertically blowing up: a minimum
of 1.4 m below the ceiling.
The position of the gas regulator
block depends on the heater set-up,
see fig. 6.
Warning
The heater is suited for a gas
pressure of 50 mbar maximum.
When connecting to a higher gas
pressure, a pre-pressure regulator
must be included in the gas pipe, see
fig. 7 (B).
Warning
The heater may only be installed by
suitably authorised people in
accordance with the local standards.
Warning
This check may only be performed by
a suitably authorised person.
The toestellen are adjusted and
regulated for use on natural gas G25
(I2L).
If the yellow control light of the burner
automat is lit, the plug in the socket
must be reversed.
The plug must always be accessible.
Hot
Do not touch the blower outlet! The
blower outlet becomes hot during
operation!
Summary of Contents for AGA 45
Page 3: ...AGA 45 75 40 020 948 rev 05 2017 3 i 6 7 8 9 10 11 A B A C B D A 5 0 5 A...
Page 46: ...46 40 020 948 rev 05 2017 AGA 45 75 P 47 48 49 50 51 52 54 54 55 E 55 1 A B C D E F G H I J K...
Page 47: ...AGA 45 75 40 020 948 rev 05 2017 47 p 1 1 1 1 2 2 A B C 1 3 1 4 3...
Page 51: ...AGA 45 75 40 020 948 rev 05 2017 51 p 5 5 1 i X X X X X X X X X...
Page 52: ...52 40 020 948 rev 05 2017 AGA 45 75 P 5 2 1 2 3 5 3 1 2 10 3 6 6 1 i 1 2 3 4 5...
Page 53: ...AGA 45 75 40 020 948 rev 05 2017 53 p 7 8 9 10 11 12...
Page 54: ...54 40 020 948 rev 05 2017 AGA 45 75 P 7 8 13 10 14 11 15 16...