The gas enters the burner through the nozzle
and is mixed with air. The mixture is ignited
with an electrical spark. An ionisation
electrode is used to check if a flame occurs
within a few seconds. If there is no flame
within the prescribed time, the heater triggers
an error. The ignition stops automatically
when a good flame is formed.
The heater is equipped with a digital burner
automat that monitors and checks the ignition
and the gas supply. If the gas pressure falls
below a certain minimum value, the gas block
disconnects the gas supply. The burner
automat also checks the flame during
operation through ionisation measurement.
To be sure that sufficient combustion air is
fed to the burner, the combustion air pressure
is measured immediately after the fan and in
the burner head. If the pressure difference
between the two measurement points is too
low, the heater triggers an error.
With an error, the burner automat switches
the heater off. Now, the red lamp on the
operating panel lights. It is possible to
connect an external alarm (consult the
dealer).
The heater is equipped with two thermostats
to control the temperature. The thermostat
after the burner has an automatic reset, the
thermostat on the cooling jacket must be
manually reset.
The heater stops when the selector switch on
the operating panel is set to “Off”. The heater
can be used as a fan by setting the selector
switch on the operating panel to “Ventilate”.
2.3
Main components of the heater
(fig. 3)
A Exhaust grid
B Combustion chamber
C Thermostat with reset button
D Thermostat with automatic reset
E Combustion air fan
F
Operating panel
G Inlet grid
H Hot air fan
I
Gas block
J
Pictograms
2.4
Main components of the
combustion chamber (fig. 4)
A Combustion chamber
B Ignition electrode
C Burner head
D Nozzle
E Burner
F
Ionisation electrode
2.5
Control panel (fig. 5)
A Reset button
B Indicator light (red) malfunction
C Indicator light (orange) burner automat
D Selector switch:
-
0: Off
-
1: Heat
-
2: Ventilate (not heat)
E Connection point for room thermostat
F
Connection cable
2.6
Thermostat
The heater has two maximum thermostats
that switch the heater off when the maximum
permissible temperature of the hot air is
exceeded.
2.7
Accessories
•
Room thermostat
•
Pre-pressure regulator
•
Outside-air suction hose
•
Outside air feed-through
Summary of Contents for AGA 45
Page 3: ...AGA 45 75 40 020 948 rev 05 2017 3 i 6 7 8 9 10 11 A B A C B D A 5 0 5 A...
Page 46: ...46 40 020 948 rev 05 2017 AGA 45 75 P 47 48 49 50 51 52 54 54 55 E 55 1 A B C D E F G H I J K...
Page 47: ...AGA 45 75 40 020 948 rev 05 2017 47 p 1 1 1 1 2 2 A B C 1 3 1 4 3...
Page 51: ...AGA 45 75 40 020 948 rev 05 2017 51 p 5 5 1 i X X X X X X X X X...
Page 52: ...52 40 020 948 rev 05 2017 AGA 45 75 P 5 2 1 2 3 5 3 1 2 10 3 6 6 1 i 1 2 3 4 5...
Page 53: ...AGA 45 75 40 020 948 rev 05 2017 53 p 7 8 9 10 11 12...
Page 54: ...54 40 020 948 rev 05 2017 AGA 45 75 P 7 8 13 10 14 11 15 16...