Tanks are cooled during the night.

Does collector circuit 
pump run during the 
night?

no

yes

Check the controller 
functions

Collector temperature is 
at night higher than ambi-
ent temperature.

no

yes

Check  the  return  flow 
preventer in feed flow and 
return flow with regard to 
the functional efficiency.

Is tank insulation suffi-
cient?

yes

no

Intensify the insulation.

Is tank insulation close 
enough to the tank?

yes

no

Replace or intensify the 
insulation.

Are the tank connections 
insulated?

yes

no

Insulate connections.

Warm water outflow 
upwards?

no

yes

Change connection and 
let the water flow side-
wards or through a siphon 
(bow  downwards);  less 
tank losses now?

Does warm water circu-
lation run for a very long 
time?

no

yes

Use the circulation pump         
with timer and switch-off 
thermostat (energy effi-
cient circulation)

The solar circuit pump does not work although the coll-
ector is obviously warmer than the tank.

Does the control LED 
flash?

yes

no

Does the pump start up 
in manual operation?

yes

There is no current; check 
fuses / replace them and 
check power supply.

The adjusted temperature 
difference for starting the 
pump is too high; choose 
an matching setting

no

Is the current of the 
pump released by the 
controller?

yes

Is the pump stuck?

Put the pump into operati-
on by means of a screwdri-
ver; is it passable now ?

Is the pump defective - 
replace it.

Are the fuses of the 
controller o.k.?

Controller seems to be 
defective - replace it.

no

yes

no

no

yes

Replace the fuses.

Switch-off the circulation 
pump  and  the  blocking 
valve for 1 night; less tank 
losses?

yes

no

Check the pumps of the 
after-heating circuit ac-
cording to nightly run and 
defect return flow preven-
ter; problem solved?

no

no

yes

o.k.

Control the return flow 
preventer in warm water 
circulation- o.k.

yes

no

Please also check further 
pumps which are connec-
ted to the solar tank.

The gravitation circulation 
in the circulation line is 
too strong; insert a stron-
ger return flow preventer 
or an electrical 2-way val-
ve behind the circulation 
pump; the 2-way valve is 
open  in  pump  operati-
on, otherwise it is closed, 
conect pump and 2-way 

Cleaning or replacement.

valve in parallel; activate 
the circulation again!

a

a

b

b

Summary of Contents for USDT 3002

Page 1: ...USDT 3002 Thanks for buying Read this manual carefully to get the best perfomance from this unit USDT 3002 Unit Mounting Power Connections Operation Troubleshooting manual ...

Page 2: ...ted Any use outside of the copyright requires the approval of Thermo Technologies This especially applies for copies translations micro films and electronic storage media Editor Thermo Technologies Important notice Accuracy of all texts and drawings in this manual are to the best of Thermo Technologies knowledge and consent The information and illustrations contained in this manual should act only ...

Page 3: ...40050 Environmental temp 0 104 F Size 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Power supply 115V Total power supply 2 x 1 A Mode of operation Typ 1 b Breaking capacity per relay electromechanical relay 2 x 1 A At the factory USDT 3002 is set to control a standard solar water heating system with an auxiliary relay to divert surplus heat The auxiliary relay can...

Page 4: ... The power supply to the controller must be via an external power supply switch last step of installation and the line voltage must be 115 Volt 50 60 Hz Flexible lines are to be fixed at the housing by enclosed strain relief supports and screws The controller is equipped with 2 relays for connection to system counterparts e g pumps valves etc can be con nected Relay 1 18 conductor R1 17 neutral con...

Page 5: ...d 2nd relay R2 The sensor S4 TRF can optionally be used fas a flow meter or a 4th temperature sensor Arr 2 1 2 2 Allocation of terminals for system 2 Arr 2 Symbol Specification S1 collector sensor S2 tank sensor below S3 tank sensor at the top S4 TRF optional sensor for flow meter additional tempe rature input R1 solar pump R2 pump for heat exchange Symbol Specification S1 Collector sensor S2 Tank sen...

Page 6: ...crolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function Select a channel channel using the forward back keys 1 and 2 Briefly press the center key so that SEt flashes Adjust the value using the foward back keys then briefly press the center key so that SEt permanently appearsThe adjusted value is now saved Addit...

Page 7: ...r sensor Pump 3 way valves The flow direction or the current bre aking capacity are always shown Heating circuit Tank 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only system screen Constantly green System functioning correctly Red green blinking blinking initialisation phase of manual operation Red blinking sensor defect 2 3 Blinking codes 2 3...

Page 8: ...ing channel is only available if the option heat quantity measurement is deactivated OWMZ Please note S3 and S4 are only indicated if sensors are connected channel Arr specification page 1 2 COL x x Temperature collector 1 9 TST x Temperature tank 1 9 TSTL x Temperature tank 1 below 9 TSTU x Temperature tank 1 above 9 S3 x Temperature sensor 3 9 TRF Temperature return sensor 9 S4 Temperature sensor...

Page 9: ...e operating hours counter adds up the solar operating hours of the respective relay h P Completed hours are shown on the display and may be reset back to 0 Select the operating hours channel h P The center button for approx 2 seconds in order to get back into the RESET mode of the counter The display symbol is flashing and the operating hours will be set to 0 Press the center button again to save t...

Page 10: ...he switch off temperature difference DF DT O Switch on temperature Adjustment range 2 0 40 0 Ra Factory setting 12 0 DT F Switch off temperature diff Adjustment range 1 0 38 Ra Factory setting 8 0 Ra Primarily the controller works in the same way as a standard differential controller If the switch on difference DTO is reached the pump is activated If the adjusted switch off temperature is underrun...

Page 11: ...ustment range OFF ON Factory setting OFF The minimum collector temperature must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a steady starting up of the solar pump or solid fuel boiler charging pumps for low collector temperatures If the minimum temperature is underrun in the display is shown flashing 4 1 13 Recooling function 4 1 12 Antifreeze functio...

Page 12: ...ed for storage of surplus energy or after heating AH O AH F the 2nd relay is used for after heating AH O AH F the 2nd relay is used for use of surplus energy On the display is shown if the second relay output is activated 4 1 15Thermostat function Arr 2 after heating use of surplus energy AH O 2nd relay switch on temperature Adjustment range 32 203 F Factory setting 104 F AH F 2nd relay switch off...

Page 13: ...over spare fuse is enclosed in the accessory bag Operating control lamp flashes red On the display appears the symbol and the symbol Sensor defect An error code is shown on the relevant sensor indication channel instead of a temperature 88 8 888 8 Line break Check the line Short circuit Check the line Pt1000 temperature sensors pinched off can be checked with an ohmmeter In the following the resist...

Page 14: ... replace Decalification no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and Toff accordingly Switch on temperatu re difference Ton too large no yes Collector sensor unfavor able placed e g contact sensor instead of immersion sleeve sensor o k no Pump is overheate...

Page 15: ...p in manual operation yes There is no current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is too high choose an matching setting no Is the current of the pump released by the controller yes Is the pump stuck Put the pump into operati on by means of a screwdri ver is it passable now Is the pump defective replace it Are the fuses of the c...

Page 16: ... thermomax com 6 Accessories Overvoltage protection We highly recommend installing the overvoltage protection in order to avoid damages at the collector e g by lighte ning Sensors Our product range includes high precision temperature sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiation sensors also to be used as full sensors wi...

Reviews: