4
WARNING:
All wiring must be installed by a certified electrician according to the electrical safety.
The ceiling heater must be grounded in accordance with all national and local building codes.
All Wiring procedures and connections shall be in accordance with the national and local
codes having jurisdiction.
NOTE: Compatible with a 240V Line Voltage Double Pole Wall Thermostat. Must be installed
by a Certified Electrician.
Before installation:
Disconnect the main supply connection.
Supply cables shall be 10 AWG (5.3 mm
2
) copper wires
The heater must be connected to individual branch circuit protected by 30 Amp circuit breaker only.
Supply cables must be equipped with a dual pole circuit breaker rating at least 240V 30A/pole as
main cutoff switch of power connection to the heater.
CAUTION
:
High temperature, risk of fire, keep electrical cords, drapery, furnishings, and other
combustibles at least 3 feet (0.9 m) from the front of the heater and away from the side and rear.
WARNING:
To reduce the risk of fire, do not store or use gasoline or other flammable vapors and
liquids in the vicinity of the heater.
INSTALLATION INSTRUCTION:
1. Keep the unit at least 6 feet (1.8 m) away from the floor. This minimum distance must be
maintained.
2. Do not install closer than1 foot (or 0.3 m) to any adjacent vertical surfaces or walls.
3. Keep at least 4.5 inches (11.5 cm) from the back wall (with or without using the wall hanging
mounting bracket).
4. Mark the drill-hole positions in the wall or ceiling for the mounting bracket.
5. Drill the required holes with diameter fit for the anchor provided for positioning the mounting
bracket.
6. Insert the anchors.
7. Attach the mounting bracket to the wall or ceiling and secure with mounting screws.
8. Hook the unit to the mounting bracket and let the unit hang from the mounting bracket.
INSTALLATION INSTRUCTIONS
WALL MOUNT
CEILING MOUNT