background image

8

Thermo Scientific Jewett Blood Bank Refrigerators

Installation and Operation

10 Chart Recorders

Panel-mounted six inch recorders are standard and factory-
installed on all models except for undercounter models, for 
which free-standing recorders are available as options. 

Recorder operation begins when the system is powered on.

10.1 Set Up and Operation

To prepare the recorder to function properly, complete the 
following steps:

1. Open the recorder door to access the recorder.
2. Connect the nine volt DC battery located at the recorder’s 

upper right corner. This battery provides back-up power.

3. Install clean chart paper (refer to Section 10.3 below).
4. Remove the plastic cap from the pen stylus and close the 

recorder door.

Note:

The recorder may not respond until the system reaches 

temperatures within the recorder’s range. 

Figure 5.  Six Inch Chart Recorder

Figure 6.  Chart Buttons

10.2 Power Supply

The recorder normally uses AC power when the system is 
operating. If AC power fails, the LED indicator flashes to alert 
you to a power failure. The recorder continues sensing cabinet 
temperature and the chart continues turning for approximately 

24 hours with back-up power provided by the nine-volt battery. 

The LED indicator glows continuously when main power is 
functioning and the battery is charged.

When the battery is low, the LED flashes to indicate that the 
battery needs to be changed.

10.3 Changing Chart Paper

To change the chart paper, complete the following steps:

1. Locate the pressure sensitive buttons at the front, upper left 

of the recorder panel.

2. Press and hold the change chart button for one second. The 

pen will move off the scale.

3. Unscrew the center nut, remove the old chart paper, and 

install new chart paper. Carefully align the day and time with 

the reference mark on the recorder panel (a small groove on 
the left side of the panel, shown in Figure 5).

4. Replace the center nut and hand tighten. Press the change 

chart button again to resume temperature recording.

10.4 Calibration Adjustment

This recorder has been accurately calibrated at the factory and 
retains calibration even during power interruptions. If required, 

however, adjustments can be made as follows:

1. Run the unit continuously at the control setpoint temperature. 

Continue steady operation for at least two hours to provide 

adequate time for recorder response.

2. Measure cabinet center solution temperature with a 

calibrated temperature monitor. (Solution temperature is 

measured inside the sensor bottles — see Section 8.2.)

3. Compare the recorder temperature to the solution 

temperature. If necessary, adjust recorder by pressing the left 

(#1) and right (#2) chart buttons.

Note:

The stylus does not begin to move until the button is held 
for five seconds.

9 Volt Battery

Imprinting

Stylus

Hub-Nut and

Retaining Wire

Chart

Chart Buttons

Reference Mark

1

2

3

CHANGE CHART

Summary of Contents for Jewett JBB1204

Page 1: ...Installation and Operation Manual Thermo Scientific Jewett Blood Bank Refrigerators ...

Page 2: ... 2010 Thermo Fisher Scientific All rights reserved Suva is a registered trademark of DuPont All other trademarks are the property of Thermo Fisher Scientific Inc and its subsidiaries ...

Page 3: ...Hinged Glass Doors Undercounter Models Only 2 4 5 Door Seal 3 4 6 Final Checks 3 5 Drawers 3 5 1 Removing the Drawers 3 5 2 Reinstalling the Drawers 3 5 3 Changing Drawer Slide Position 3 5 4 Control Panel Features 4 6 Control Panel 4 6 1 Display Functions 5 6 2 Programming Functions 5 6 3 Service Parameters 5 7 Operation 6 7 1 Start Up 6 7 2 Product Loading Guidelines 6 7 3 Automatic Defrost 6 8 ...

Page 4: ...9 3 Installing a Remote Alarm Optional 7 9 4 Alarm Test 7 9 4 1 Theory of Operation 7 9 4 2 Alarm Test Procedure 7 10 Chart Recorders 8 10 1 Set Up and Operation 8 10 2 Power Supply 8 10 3 Changing Chart Paper 8 10 4 Calibration Adjustment 8 11 Cleaning 9 11 1 Cleaning the Drawers and Cabinet Interior 9 11 2 Cleaning the Condenser 9 12 Troubleshooting 10 ...

Page 5: ... product warning labels carefully Failure to follow these instructions may cause this product to malfunction which could result in injury or damage Below are important safety precautions that apply to this product Use this product only in the way described in the product literature and in this manual Before using it verify that this product is suitable for its intended use Do not modify system com...

Page 6: ...rloaded power lines Always connect the equipment to a dedicated separate circuit Electrical codes require fuse or circuit breaker protection for branch circuit conductors Use time delay fuses for 12 AWG circuits For all blood bank models the wiring diagram is attached to the back of the cabinet 4 3 Leveling The unit must be level Rotate the leveling screws located under the front corners of the un...

Page 7: ...age the mounting tabs from the slots on the slides Note The drawers fit snugly between the slides Push the back of the drawer from underneath to remove the drawer 3 Raise the back of the drawer almost to a vertical position and disengage the front mounting clips from the slides To remove the drawers on Space Saver models depress the hooks located on both sides of the drawers about 1 3 of the way b...

Page 8: ...of bars illuminated indicates cabinet temperature as follows bulb only 0ºC cold alarm 6 bars 4 8 1 bar 0 8 7 bars 5 6 2 bars 1 6 8 bars 6 4 3 bars 2 4 9 bars 7 2 4 bars 3 2 10 bars 8 warm alarm 5 bars 4 setpoint When cabinet temperature exceeds the warm alarm setpoint the top bar of the thermometer flashes When temperature is lower than the cold alarm setpoint the bulb flashes When you are in prog...

Page 9: ...ss and simultaneously hold for five seconds Excursion values are reset temperature display shows cabinet temperature Alarm test Test by simulating warm alarm conditions key switch must be in alarm mode Press and Scan simultaneously Display and thermometer show simulated cabinet temperature alarms flash and sound as appropriate Alarms clear when test is completed Lower sensor Display lower cabinet ...

Page 10: ...re you load any product 7 3 Automatic Defrost The defrosting process on all models is primarily accomplished by air circulated during off cycle periods Under normal conditions the temperature warm up during defrost is virtually unnoticeable However an occasional 2 C warm up is possible if usage is heavy and ambient conditions are extreme 8 Temperature Control 8 1 Setpoint Control Your individual u...

Page 11: ...ail wire on the alarm The purple and red white wires must be tied together in this application The wiring diagram is attached to the inside of the alarm back cover 9 4 Alarm Test Note It is important to test your alarm system after any maintenance operation or temperature control adjustment 9 4 1 Theory of Operation This test procedure applies to both factory installed built in alarms and optional...

Page 12: ...s low the LED flashes to indicate that the battery needs to be changed 10 3 Changing Chart Paper To change the chart paper complete the following steps 1 Locate the pressure sensitive buttons at the front upper left of the recorder panel 2 Press and hold the change chart button for one second The pen will move off the scale 3 Unscrew the center nut remove the old chart paper and install new chart ...

Page 13: ...ols CAUTION Condensers should be cleaned at least every six months In heavy traffic areas condensers load with dirt more quickly Failure to keep the condenser clean can result in equipment warm up or erratic temperatures CAUTION Never clean near condensers with your fingers Some surfaces are sharp Periodically check the condenser to make sure that it is clean In all models the condenser is located...

Page 14: ... is clean but temperature continues to fluctuate call an authorized service representative Unit warms up Door is open Make sure the door is completely closed Door seal Check the door seal following instructions in Section 4 5 on page 3 Warm product recently loaded in unit Allow ample time to recover from loading warm product Power supply Check for proper voltage to the unit If there is no voltage ...

Page 15: ...iese RoHS Anweisungfallen finden Sie unter www thermo com Conformità WEEE Questo prodotto deve rispondere alla direttiva dell Unione Europea 2002 96EC in merito ai Rifiuti degli Apparecchi Elettrici ed Elettronici WEEE È marcato col seguente simbolo Thermo Fischer Scientific ha stipulato contratti con una o diverse società di riciclaggio smaltimento in ognuno degli Stati Membri Europei Questo prod...

Page 16: ...ve information can be found on the dataplate attached to the equipment If available please provide the date purchased the source of purchase manufacturer or specific agent rep organization and purchase order number IF YOU NEED ASSISTANCE SALES DIVISION Phone 1 866 984 3766 866 9 THERMO LABORATORY PARTS and SERVICE Phone 1 800 438 4851 TECHNICAL SUPPORT Phone 1 800 438 4851 ...

Page 17: ...Thermo Fisher Scientific Inc 275 Aiken Road Asheville NC 28804 United States www thermofisher com 34830H54 Rev A ...

Reviews: