MEB Options
2-PI MEB
Table 4–12. Discrete outputs on the 4-DO MEB
Input
SIG
GND
DO1
TB2-2
TB2-3
DO2
TB2-4
TB2-5
DO3
TB2-6
TB2-7
DO4
TB2-8
TB2-9
With the 2-PI MEB installed, the flow computer will accept two pulse
inputs from customer input devices such as reed switches, slot sensors,
magnetic pick-up, and uncommitted transistor outputs. Up to four boards
may be installed in the unit.
A unique address that determines the software configuration must be set
using jumpers JP1 and JP2 for each 2-PI MEB installed. The address
jumpers are configured as shown in the table below.
Table 4–13. Address jumper configuration for 2-PI MEB
Board #
JP1
JP2
1
Not installed
Not installed
2
Not installed
Installed
3
Installed
Not installed
4
Installed
Installed
After installing the MEB according to
earlier in this chapter,
connect TB2 on the 2-PI MEB to the MEB terminal block (TB2) on the
enclosure door panel as shown below.
Table 4–14. 2-PI MEB to TB2 connections
Color
TB2 on 2-PI MEB
TB2 on Enclosure Door
Blue
TB2-3 (+5V)
TB2-3 (VCC)
Yellow
TB2-2 (SDA)
TB2-4 (SDA)
White
TB2-1 (SCL)
TB2-5 (SCL)
2-PI MEB
Address Jumpers
Connection to MEB
Terminal Block
Thermo Fisher Scientific
AutoPILOT PRO Flow Computer User Guide 4-13