All installations and services must be performed by qualified service personnel.
7
NOTICE: Any internal stiffeners used in the filter must not be removed, although they can
be cut to size as needed.
E.
LIMIT POSITION
The limit in these furnaces are fixed and cannot be relocated.
F.
BURNER INSTALLATION:
NOTICE:
Remove all cardboard packing from around chamber before installing burner.
The oil burner will mount on three stud mounting bolts on the lower mounting plate covering the
opening in the front of the heat exchanger. The end of the burner tube should be inserted no
further than 1/4 inch back from the inside surface of the combustion chamber. A distance further
than 1/4 inch back from the inside chamber wall may cause impingement and sooting. This unit
is equipped with a chamber retainer (refer to Fig.3). The retainer secures the chamber during
shipping and helps to maintain insertion depth.
DO NOT remove this retainer when installing burner.
Fig. 3: Typical location of the over fire air tap and components in burner mounting plate
area
Summary of Contents for OL6FA072D48B
Page 2: ......
Page 27: ...23 All installations and services must be performed by qualified service personnel...
Page 29: ...25 All installations and services must be performed by qualified service personnel...
Page 31: ...27 All installations and services must be performed by qualified service personnel...
Page 33: ...29 All installations and services must be performed by qualified service personnel...
Page 34: ...30 All installations and services must be performed by qualified service personnel...
Page 35: ...31 All installations and services must be performed by qualified service personnel...
Page 36: ...32 All installations and services must be performed by qualified service personnel...
Page 37: ...33 All installations and services must be performed by qualified service personnel 57...
Page 38: ...34 All installations and services must be performed by qualified service personnel...
Page 39: ...35 All installations and services must be performed by qualified service personnel...
Page 50: ...46 All installations and services must be performed by qualified service personnel OL8RA119T60...