background image

All installations and services must be performed by qualified service personnel. 

 

 
II.  GENERAL INSTRUCTIONS - READ BEFORE START OF INSTALLATION 

 
1. The heating output capacity of the furnace proposed for installation should be based on a heat loss calculation 
made according to the manuals provided by the Air Conditioning Contractors of America (ACCA) or the American 
Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE). 
 
2. All local codes and/or regulations take precedence over the instructions in this manual and should be followed 
accordingly. In the absence of local codes, installation must conform with these instructions and regulations of the 
National Fire Protection Association, and to the provisions of the National Electrical Code (ANSI/NFPA 70-1999 or 
latest edition).  
 
3. The installed furnace must be level and positioned in a central location with respect to outlet registers. It should 
be located near the chimney to minimize any horizontal run of flue pipe, which may be required. 
 
4. A furnace installed in a residential garage must be installed so the burner and ignition source are located higher 
than 18 inches above the floor, unless the required combustion air is taken from the exterior of the garage. Also, the 
furnace must be located or protected to avoid physical damage by vehicles. 
 

c

WARNING:

 This furnace is not to be used as a construction heater.  

 
5. Listed below are definitions of "COMBUSTIBLE MATERIAL" and "NON-COMBUSTIBLE MATERIAL." 
 

COMBUSTIBLE MATERIAL:

 

Material made of or surfaced with wood, compressed paper, plant fibers, plastics, or other material that will ignite 
and burn, whether flame resistant or not. 
 

NON-COMBUSTIBLE MATERIAL: 

Material that is not capable of being ignited and burned.  Such materials consist entirely of, or a combination of, 
steel, iron, brick, tile, concrete, slate, or glass.   
 

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS 

 

TYPE OF UNIT 

MODEL NO.

1

 

FROM 

SIDES OF 

FURNACE 

FRONT 

TOP & 

SIDES OF 

PLENUM 

FROM THE 

FLUE/VENT 

REAR 

HIGHBOY 

OH5-85DXE*** 1 

24  1 

 

 

 

 

 
The minimum clearances listed in the preceding table are for fire protection.  Clearance for servicing the front of the 
furnace and the rear of the lowboy models should be at least 24 inches.  A clearance of 24 inches is recommended 
for passage to all points on the furnace requiring service access.   
 
The OH5-85DXE*** furnaces may be installed on combustible flooring.  
 

NOTE: 

The OH5-85DXE*** furnace is approved for closet installation. If the OH5-85DXE*** is installed in a 

closet, it requires two openings in the closet door for combustion air, each having a minimum area of 162 sq. inches.  
This free area for the OH5-85DXE*** intentionally exceeds the recommended minimum free area of 2 square 
inches per 1000 BTUH of input rate. 
 

NOTE:  

When power venting a Thermo Pride oil fired furnace with a power venting system other than the system 

supplied by Thermo Pride, a fiber chamber and an isolated combustion air kit (PVB or Beckett boot) is to be used 
with the other manufacturers power venting system. 
 

 
 

Summary of Contents for OH5-85DXE

Page 1: ...INITY OF THIS OR ANY OTHER APPLIANCE c WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY OR PROPERTY DAMAGE REFER TO THIS MANUAL FOR ASSISTANCE OR ADDITIONAL...

Page 2: ...al injury substantial property damage or death See Page 4 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 7 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page...

Page 3: ...R CONDITIONING 3 D FILTERS MOUNTED EXTERNAL TO FURNACE 3 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 5 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANING INSTRUCTIONS 8 III...

Page 4: ...sted below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MATERIAL COMBUSTIBLE MATERIAL Material made of or surfaced with wood compressed paper plant fibers plastics or other material tha...

Page 5: ...ening on left hand side of casing TRIM COLLAR UNIT DIA HOLE X DIM Y DIM FLUE DIA GASKET PART OH5 85DXE 6 1 2 4 3 4 33 1 16 6 14131 330005 FRONT FLUE MODELS ONLY X DIMENSION IS MEASURED FROM SEPARATOR...

Page 6: ...ividual coil manufacturer D FILTERS MOUNTED EXTERNAL TO FURNACE On highboy furnaces it is necessary to cut the return air opening in the side or rear casing depending upon the needs of the specific in...

Page 7: ...long the inside of the securing flange on three of the sides To scribe a line on the fourth side the open end use the open end support as a guide Remove the filter rack and cut the return air opening...

Page 8: ...limit control installed at the time of unit installation Fig 7 Limit location for OH5 85DXE F BURNER INSTALLATION The oil burner will mount on three stud mounting bolts on the lower mounting plate cov...

Page 9: ...tube end cone is properly positioned when the end is inch back from the inside surface of the combustion chamber wall NOTE The loose fill insulation that is included in a brown paper bag should be lig...

Page 10: ...AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 H NOTE The reason the Riello burner nozzle sizes are smaller than the standard Thermo Pride burner nozzles is that pre set pu...

Page 11: ...emove clean out covers the vent connector pipe to the chimney the burner and the burner mounting plates When removing the clean out covers special care must be taken not to damage the gaskets Should t...

Page 12: ...furnace and looking for signs of excessive heat such as discoloration of components materials damage from rust or corrosion soot or carbon build up EXTERIOR OF FURNACE The furnace exterior should be...

Page 13: ...filters frequently may reduce airborne contaminants from entering the furnace and depositing in the furnace duct system and home cWARNING To avoid injury from moving parts hot surfaces or electrical...

Page 14: ...HIMNEY W INDUCER MASONRY CHIMNEY W METAL LINER FUEL LINE FILTER DRAFT CONTROL COMBUSTION TESTS Operate burner at least 10 minutes before CO2 in stack pipe INITIAL SERVICE SERVICE SERVICE INSTALLATION...

Page 15: ...All installations and services must be performed by qualified service personnel 12 APPENDIX A Replacement Parts List...

Page 16: ...All installations and services must be performed by qualified service personnel 13 APPENDIX B Wiring Diagram...

Page 17: ......

Reviews: