Alarms

The Red Alarm Symbol will illuminate in the following two 
conditions:
• high or low pressure switches are off longer than 10 minutes
• high or low pressure switches are off 5 times per 10 minutes 

(flash on and off).

In both cases, the unit will switch to the Ventilation mode.
The Yellow Alarm Symbol will illuminate in case of temperature 
sensors failure.
Yellow Alarm number will be shown on the display for 5 seconds.
Red Alarm number will stay on the display till any button is pushed.
To restart the unit, press twice the key ON/OFF (1) to switch OFF 
and ON the unit.

Warranty Instructions

Should you require warranty service during the warranty period, 
simply present your copy of the Warranty Certificate at any of the 
dealer locations shown in the Thermo King Service Directory. Terms 
of the complete Thermo King Corporation Warranty are available on 
request.

Controller 

Operator’s 

Manual

Control Panel Descriptions

Operating Instructions

Alarms

ATTENTION: If the alarm comes up again, don’t 
restart and see your nearest dealer for service.

CAUTION: The unit can automatically start and run 
anytime the ignition key is in the ON or OFF position.
No matter if the ON/OFF switch is ON or OFF 
(depends on setup program).