Refrigeration Maintenance (Rev. 04/03)
64
Set Up and Test of Evacuation Equipment
NOTE: Refer to the previous two pages for the following
discussion.
1.
Connect the evacuation system to a 110 V ac power
supply. Connect a gauge manifold and refrigerant sup-
ply to the fitting above valve V-4. Turn the micron
gauge ON.
2.
Close valves V-1, V-3 and V-4. Valve V-2 is open.
3.
Turn the vacuum pump ON.
4.
Open valve V-1 at the pump. The micron gauge needle
will move to the left. (Refer to micron gauge scale dia-
gram—previous page.)
LEAK
Isolate the pump from the system by closing the
proper valve. Watch the movement of the vacuum
gauge needle. If the needle continues to rise, this is an
indication that a leak exists in the unit or the connect-
ing line. The leak must then be located and eliminated.
NOTE: If the vacuum pump is okay, and there are no
leaks between V-1 and V-3, the micron gauge should
show less than 500 microns. If not, locate and correct
the problem.
5.
With the pump still operating, open valve V-3. If the
micron reading does not return to a level of less than
500 microns, locate and correct the problem before
continuing.
6.
With the vacuum pump still operating, open valve V-4.
The micron level will rise momentarily. If the micron
reading does not return to a level of less than 500
microns, locate and correct the problem before continu-
ing.
MOISTURE
Should the needle show a pressure rise but finally
level off to practically a constant mark, this is an indi-
cation that the system is vacuum tight but is still too
wet, requiring additional dehydration and pumping
time.
Summary of Contents for 088669
Page 4: ......
Page 8: ......
Page 12: ...Safety Precautions Rev 04 03 iv PUB126...
Page 13: ...Safety Precautions Rev 04 03 v aea105...
Page 14: ......
Page 28: ...Unit Description Rev 04 03 14 Rear View Curbside RD II SR Evaporator aea105...
Page 32: ...Unit Description Rev 04 03 18 Power Receptacle Box RD II SR 50 aea102...
Page 76: ...Refrigeration Maintenance Rev 04 03 62...
Page 77: ...Refrigeration Maintenance Rev 04 03 63...
Page 81: ...Refrigeration Maintenance Rev 04 03 67...
Page 103: ...89 Hilliard Clutch Maintenance Clutch Assembly...
Page 106: ...Hilliard Clutch Maintenance Rev 04 03 92 12 Install retaining ring Clutch Torque Values...
Page 125: ...111 Cool Cycle RD II SR with TherMax Heating...
Page 126: ...112 Condenser Cycle RD II SR with TherMax Heating...
Page 127: ...113 Heat and Defrost Cycle RD II SR with TherMax Heating...
Page 129: ...115...
Page 130: ...116...
Page 131: ...117...
Page 132: ...118...
Page 133: ...119...
Page 134: ...120...
Page 135: ...121...
Page 136: ...122...