8.
At this screen:
a.
Scroll to the required totalizer unit (US gallons, Imperial gallons,
million gallons, cubic feet, cubic meters, liters, oil barrels, liquid
barrels) and press Enter.
b.
Scroll through the available scale factors (x 1, 10, 100, 1000,
10000), and press Enter to select.
c.
Determine whether to reset the totalizer and scroll to the
appropriate selection. Press Enter.
9.
Set the range at this screen:
a.
Enter the flow rate that equals the 4 mA (minimum) reading, and
press Enter.
b.
Enter the flow rate that equals the 20 mA (maximum) reading, and
press Enter.
c.
Select Next to move to the next setup screen.
10.
Set the time and date at this screen, and press Next to continue.
11.
Scroll through the available wall material options (carbon steel, cast
iron, concrete liner, stainless steel, copper, plastic) and press Enter to
select. Press Next to complete the configuration process.
You can also use the HydraScan software to configure the instrument.
Refer to the HydraScan user guide (P/N 1-0563-005).