22
INSTALLER/SERVICEMAN
Fixed Pressure and Variable Orifice
Model Number
CWL-GS-120
CWL-GS-140
CWL-GS-160
Burner Type
Heat Wise
Heat Wise
Heat Wise
Burner Model
SU-2A
SU-2A
SU-2A
Fuel
Nat. Gas
Nat. Gas
Nat. Gas
Orifice
15/64"
1/4"
19/64"
Max Inlet Pressure
11"
11"
11"
Min Inlet Pressure
5"
5"
5"
Manifold Pressure
3.5"
3.5"
3.5"
Head Position
11
11
11
Air Shutter
12.50
15.00
20.75
Draft Over Fire
+ 0.04"
+ 0.06"
+ 0.08"
Draft In Stack
-0.02"
-0.02"
-0.02"
CO
2
Reading
9.0%
9.0%
9.0%
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. See installation/service manual for
detailed information.
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
INSTALLER/SERVICEMAN
CWL-GS DIRECT VENT
Fixed Pressure and Variable Orifice
Model Number
CWL-GS-120DV
CWL-GS-140DV
CWL-GS-160DV
Burner Type
Heat Wise
Heat Wise
Heat Wise
Burner Model
SU-2A
SU-2A
SU-2A
Fuel
Nat. Gas
Nat. Gas
Nat. Gas
Orifice
15/64"
1/4"
19/64"
Max Inlet Pressure
11"
11"
11"
Min Inlet Pressure
5"
5"
5"
Manifold Pressure
3.5"
3.5"
3.5"
Head Position
11
11
11
Air Shutter
12.50
15.00
20.75
Draft Over Fire
+ 0.10"
+ 0.14"
+ 0.18"
Draft In Stack
-0.06"
-0.08"
-0.10"
CO
2
Reading
9.0%
9.0%
9.0%
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. See installation/service manual for
detailed information.
INSTALLER/SERVICEMAN
Fixed Pressure and Variable Orifice
Model Number
CWL-GS-120
CWL-GS-140
CWL-GS-160
Burner Type
Heat Wise
Heat Wise
Heat Wise
Burner Model
SU-2A
SU-2A
SU-2A
Fuel
LP Gas
LP Gas
LP Gas
Orifice
15/64"
1/4"
19/64"
Max Inlet Pressure
11"
11"
11"
Min Inlet Pressure
4.5"
4.5"
4.5"
Manifold Pressure
2.3"
2.3"
2.3"
Head Position
11
11
11
Air Shutter
14.50
17.00
20.25
Draft Over Fire
+ 0.04"
+ 0.06"
+ 0.08"
Draft In Stack
-0.02"
-0.02"
-0.02"
CO
2
Reading
11%
11%
11%
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. See installation/service manual for
detailed information.
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
_________________________
INSTALLER/SERVICEMAN
CWL-GS DIRECT VENT
Fixed Pressure and Variable Orifice
Model Number
CWL-GS-120DV
CWL-GS-140DV
CWL-GS-160DV
Burner Type
Heat Wise
Heat Wise
Heat Wise
Burner Model
SU-2A
SU-2A
SU-2A
Fuel
LP Gas
LP Gas
LP Gas
Orifice
15/64"
1/4"
19/64"
Max Inlet Pressure
11"
11"
11"
Min Inlet Pressure
4.5"
4.5"
4.5"
Manifold Pressure
2.3"
2.3"
2.3"
Head Position
11
11
11
Air Shutter
15.50
17.75
21.00
Draft Over Fire
+ 0.10"
+ 0.14"
+ 0.18"
Draft In Stack
-0.06"
-0.08"
-0.10"
CO
2
Reading
11.0%
11.0%
11.0%
NOTICE
Above settings are approximate. Final adjustments to be made
with proper test equipment. See installation/service manual for
detailed information.