TURBOMAX Use and Care Manual with Installation Instructions July 2014  Page 

11

 

 

DOMESTIC HOT WATER TEMPERATURE 
& PRESSURE RELIEF VALVE 

An automatic temperature & pressure relief valve 
with a temperature probe of sufficient length must 
be installed at the time of the installation. No valve 
of any type should be placed between the T&P 
relief valve and the water heater.  Use a tee to 
install the relief valve onto the hot water outlet.  
The pressure rating of the relief valve must not 
exceed 150 psi. 
 
The BTU per hour rating of the relief valve must 
equal or exceed the BTU per hour input of the 
boiler(s) or heat source(s) as marked on the 
boiler(s) rating plate. 
 
For a circulating tank installation, the separate 
storage tank(s) must have similar protection.   
 
Connect the outlet of the relief valve to a suitable 
open drain, so discharge can exit only 6” above 
the structural floor; and cannot contact any live 
electrical parts.  The discharge line must pitch 
downward from the valve to allow complete 
draining (by gravity) of the relief valve and 
discharge line, and be no smaller than the outlet 
of the valve.  The end of the discharge line should 
not be threaded or concealed and should be 
protected from freezing.  No valve of any type, 
restriction or reducer coupling should be installed 
in the discharge line.  Local codes shall govern 
the installation of relief valves. 
 

THERMOSTATIC MIXING VALVE 

When this water heater is supplying general-
purpose hot water requirements for use by 
individuals, a thermostatically controlled mixing 
valve is recommended to reduce the risk of scald 
injury.  Contact a licensed plumber or the local 
plumbing authority for further information. 

 

Keep temperature control of the mixing valve at 
the lowest setting which is satisfactory.   
 
When installing a mixing valve, locate it at the 
bottom of anti-thermosiphon loop at least 24” high 
to prevent excessive hot water from entering 
mixed water supply. 

 
VACUUM BREAKER (IF REQUIRED) 

Install a vacuum breaker (or vacuum relief valve) 
for water heater protection.  Prevents siphoning of 
the water from the system and collapse of the 
water heater. 

 

BOILER WATER CONNECTIONS 

This water heater may be connected individually, 
in multiples with others, or with an external 
storage tank containing boiler water.  If two 
TURBOMAX

®

 or more are installed, the piping 

method to be used to connect the TURBOMAX

®

 in 

parallel should be “reverse-return piping”, so boiler 
water flow rate through each TURBOMAX

®

 is 

equal. 
 
The BOILER WATER SUPPLY and BOILER 
WATER RETURN connections are clearly 
marked.  Boiler water supply connections are to 
be made to the steel pipe (threaded connection) at 
the top of the heater.  Boiler water return 
connections are to be made to the steel pipe 
(threaded connection) at the bottom of the heater. 
 
The installation of unions is recommended on the 
BOILER WATER SUPPLY and BOILER WATER 
RETURN lines, so that the water heater may be 
easily disconnected for servicing if necessary.   
 
Dielectric unions are required for protection of the 
water heater and the pipes, if dissimilar pipe 
material like galvanized pipe, copper and steel is 
used. 
 
Use only clean pipe for boiler water lines.  Local 
codes or regulations shall govern the exact type of 
material to be used. Install shutoff (ball) valves for 
servicing convenience. Thermometer(s) should be 
installed to indicate the temperature of the boiler 
water supply and return lines. 
 

Circulator zoning recommendations 

The preferred location of the circulator pumps for 
each zone is on the boiler supply, with an 
expansion tank between the boiler and the 
circulators. 
 
A flow check valve must be installed on each 
zone, preferably at the outlet side of each 
circulator pump, to prevent water flow to other 
zones when they are not demanding flow 
 

Zone valve zoning recommandations 

The preferred location of the circulator pump is on 
the boiler supply, with the expansion tank between 
the boiler and the circulator. 
 
Use zone valves with low pressure drop 
specifications, particularly on the water heater 
zone. 

Summary of Contents for VOLTMAX 23

Page 1: ...this water heater read the instructions carefully so that they may understand how to do so Any questions regarding the operation maintenance service or warranty of this water heater should be directed to the entity from whom it was purchased When all installation steps have been completed replace this installation manual in its original envelope and keep in a safe place for future reference Note C...

Page 2: ...as a drain ball valve made of brass which have a maximum working pressure of 200 psi 3 adjustable feet support the water heater for leveling The hot water heater is shipped from the factory with an ASME rated pressure relief valve set at 30psi 50 psi on model 109 65A 109A a temperature pressure gage except 23 33 and an automatic air vent The water heater is backed by a 15 year warranty on resident...

Page 3: ...source has shut off To find hot water temperature being delivered turn on a hot water faucet and place a thermometer in the hot water stream and read the thermometer The following chart details the relationship of water temperature and time with regard to scald injury and may be used as a guide in determining the safest water temperature for your applications TIME VS TEMPERATURE RELATIONSHIPS IN S...

Page 4: ...s a priority relay When the aquastat of the water heater calls for heat the relay shuts off the space heating zones giving priority to producing domestic hot water Any demand for space heating is postponed until the water heater has reached a preset level This delay in supplying the space heating zones is usually not noticed by those occupying the living space The water heater gets adequate hot wa...

Page 5: ...the water heater was purchased CORROSIVE ATMOSPHERES The heater should not be located near an air supply containing halogenated hydrocarbons or high humidity For example The air in beauty salons dry cleaning establishments photo processing labs and storage areas for liquid and powder bleaches or swimming pool chemicals often contains such hydrocarbons The limited warranty is voided when failure of...

Page 6: ...rotection of the water heater if dissimilar pipe material like galvanized pipe is used Install shutoff ball valves for servicing convenience Use only clean copper or approved plastic pipe for water connections Local codes or regulations shall govern the exact type of material to be used To minimize heat loss during non draw periods a heat trap formed from piping can be used Insulate all pipes cont...

Page 7: ... piping schematic It as to be adapted to your application 3 Install a safety valve temperature pressure on the domestic hot water line as near as possible to the hot water heater connection and before any shut off valve 4 Pipe all the safety valves and drain valves to the drain or accordingly to the code 5 When a back flow preventer or water meter or a pressure reducing valve is used on the domest...

Page 8: ...2 This is a basic piping schematic It as to be adapted to your application 3 Install a safety valve temperature pressure on the domestic hot water line as near as possible to the hot water heater connection and before any shut off valve 4 Pipe all the safety valves and drain valves to the drain or accordingly to the code 5 When a back flow preventer or water meter or a pressure reducing valve is u...

Page 9: ...TURBOMAX Use and Care Manual with Installation Instructions July 2014 Page 9 ...

Page 10: ...TURBOMAX Use and Care Manual with Installation Instructions July 2014 Page 10 ...

Page 11: ...mixed water supply VACUUM BREAKER IF REQUIRED Install a vacuum breaker or vacuum relief valve for water heater protection Prevents siphoning of the water from the system and collapse of the water heater BOILER WATER CONNECTIONS This water heater may be connected individually in multiples with others or with an external storage tank containing boiler water If two TURBOMAX or more are installed the ...

Page 12: ...loads such as domestic hot water generation the large temperature difference between the boiler and its return water can cause the boiler to become thermally shocked An experienced designer could work with other values than those proposed by looking into the TURBOMAX performance tables and use the guidelines stated above to design a state of the art system The following chart proposes a temperatur...

Page 13: ... if proper air control is provided to eliminate air and turbulence in the system the maximum flow rate can be established by the piping friction loss rate at 4 feet of water per 100 feet This allows the use of velocities higher than 4 feet per second in pipe sized 2 inches and larger Tables 1 and 2 provide friction loss values for new pipe It should be taken into consideration that as the pumping ...

Page 14: ...tem s side are expressed in p s i Example 4 What is the pressure loss of boiler water flowing through a TURBOMAX 109 at 60 GPM Answer the pressure loss is 2 feet of water Pressure loss from boiler or other equipment Information on pressure drops losses through a boiler or other equipment is obtained from the manufacturer Piping system pressure drop calculation The pressure loss from friction in a ...

Page 15: ...ves must be used with back flow preventors as required to maintain the minimum system pressure by supplying water to make up for leakage The safety relief valve installed on a hot water boiler in accordance with ASME Boiler and Pressure Vessel Code limits the maximum pressure on the boiler Since it is a safety device it should not be considered an operating control Oxygen should be excluded from t...

Page 16: ...e from an external source Any component which does not have insulated end switches must not be used unless a relay is added with the dry contacts wires to these terminals Circulator zoning wiring Components must be wired to ensure that only the circulator for each zone is powered when demand for supply water occurs in that zone An optional multi zone switching relay is available to simplify the wi...

Page 17: ...TURBOMAX Use and Care Manual with Installation Instructions July 2014 Page 17 ...

Page 18: ... 5 4 3 1 2 T T PUMP ZONE 2 R845A RELAY ZONE 2 TO ADDITIONAL R845 RELAYS FOR OTHER ZONES 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREWS PROVIDED 2 PRIORITY RELAY 2 1 WIRING CIRCULATOR ZONING WITH DOMESTIC PRIORITY BOILER THERMOSTAT TERMINAL IF HIGH MASS BOILER THE BOILER TEMPERATURE MUST BE MAINTAINED C...

Page 19: ...THERMOSTAT ZONE 2 6 5 4 3 1 2 T T PUMP ZONE 2 R845A RELAY ZONE 2 TO ADDITIONAL R845 RELAYS FOR OTHER ZONES BOILER THERMOSTAT TERMINAL 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONTROL CASE MUST BE CONNECTED TO EARTH GROUND USE GROUNDING SCREWS PROVIDED 2 2 1 WIRING CIRCULATOR ZONING IF HIGH MASS BOILER THE BOILER TEMPERATURE MUST BE MAINTAINED CONSTANT BY USING TH...

Page 20: ...TURBOMAX Use and Care Manual with Installation Instructions July 2014 Page 20 ...

Page 21: ...r Boiler water in the piping system and in the TURBOMAX tank will not flow back into the boiler if all the air is eliminated from the TURBOMAX tank and also from the supply and return lines from the boiler Ball valves must be installed on the supply line and on the return line near the boiler to isolate the TURBOMAX from the boiler Also a ball valve should be installed on the boiler supply pipe to...

Page 22: ...cold water supply line then a thermal expansion tank must be installed between the water heater and this device TURBOMAX DOMESTIC COLD WATER SUPPLY STEAM BOILER DOMESTCI HOT WATER MIXED ALL BRONZE OR STAINLESS STEEL IN LINE PUMP STEEL PIPE 40 OR COPPER TUBE TYPE L BOILER WATER PIPING GREY COLOR COPPER PIPE TYPE L DOMESTIC WATER PIPING WHITE COLOR DOMESTIC HOT WATER THERMOSTATIC MIXING VALVE BOILER...

Page 23: ...TURBOMAX Use and Care Manual with Installation Instructions July 2014 Page 23 ...

Page 24: ...ll or makeup water valve to boiler To let the air out of the TURBOMAXV tank during the fill process open the relief valve on top of the TURBOMAX Leave all shutoff valves open Return zone valve to automatic operation Check system for leaks and repair Purge air from the remaining zones if necessary Check boiler pressure gage reading afterwards 15 p s i is normal for most installations OPERATING THE ...

Page 25: ... THE WATER HEATER WITH A THERMOSTATIC MIXING VALVE A thermostatic mixing valve provides for automatic operation through the use of a thermostatic element inside the valve The element will control the mixing of the hot and cold water supply streams to provide a safe blend to connected fixtures This provides constant water temperature under different working conditions When using models which are ce...

Page 26: ... NOTE To prevent premature tank failure the air trapped inside the tank must be purged periodically use the safety relief valve installed on top of the tank to do so Before manually operating the relief valve make certain no one will be exposed to the danger of coming in contact with hot water released by safety relief valves The water may be hot enough to create a SCALD hazard The water released ...

Page 27: ... too high Lower the temperature setting of the mixing valve TURBOMAX aquastat temperature setting is too high Lower the temperature setting of the aquastat or lower the boiler temperature Improper system plumbing Compare plumbing to installation guide Water at faucet is too hot Improper system wiring Compare wiring to installation guide Boiler hi limit set too low Increase boiler hi limit Faulty b...

Page 28: ...w the aquastat from the metal jacket The water heater is equipped with an immersion well allowing the temperature sensor of the aquastat to be removed without having to drain the unit The temperature sensor of the aquastat is located behind its access panel door at the bottom section of the tank Remove the existing sensor and insert the new one in the well Screw the new aquastat to the steel jacke...

Page 29: ...10 68 3 33 3 91 2 35 1 71 1 36 0 46 14 9 17 42 58 5 47 12 19 3 59 4 46 2 54 1 95 1 46 0 52 15 9 83 48 17 5 86 13 79 3 84 5 04 2 72 2 20 1 57 0 59 16 10 48 54 08 6 25 15 47 4 10 5 66 2 90 2 47 1 67 0 66 17 6 64 17 23 4 35 6 30 3 08 2 75 1 78 0 74 18 7 04 19 08 4 61 6 97 3 26 3 04 1 88 0 82 19 7 43 21 02 4 87 7 68 3 44 3 35 1 99 0 90 20 7 82 23 04 5 12 8 41 3 62 3 67 2 09 0 98 1 35 0 35 25 9 77 34 3...

Page 30: ...1 24 0 39 14 8 43 43 39 5 20 12 82 3 00 3 27 2 21 1 53 1 34 0 45 15 9 03 49 49 5 57 14 59 3 22 3 71 2 36 1 73 1 43 0 51 16 9 63 55 99 5 94 16 48 3 43 4 18 2 52 1 95 1 53 0 57 17 10 24 62 88 6 31 18 48 3 65 4 68 2 68 2 18 1 62 0 64 18 6 68 20 58 3 86 5 20 2 84 2 42 1 72 0 71 19 7 06 22 80 4 07 5 75 2 68 2 99 1 81 0 78 20 7 43 25 13 4 29 6 33 3 15 2 94 1 91 0 86 1 34 0 36 25 9 28 38 44 5 36 9 61 3 9...

Page 31: ... 1 7 ft 2 4 ft Gate valve 1 4 closed 2 1ft 2 9 ft 3 4 ft 4 8 ft 5 6ft 7 0 ft 8 4 ft 10 0 ft 14 0 ft Gate valve 1 2 closed 12 0 ft 14 0 ft 18 0 ft 24 0 ft 28 0ft 36 0 ft 41 0 ft 52 0 ft 70 0 ft Gate valve 3 4 closed 44 0 ft 59 0 ft 70 0 ft 96 0 ft 116 0ft 146 0 ft 172 0 ft 213 0 ft 285 0 ft Globe valve open 18 0 ft 23 0 ft 29 0 ft 38 0 ft 46 0ft 58 0 ft 69 0 ft 86 0 ft 116 0 ft Angle valve open 9 0...

Page 32: ...5 70 75 80 85 90 95 100 105 110 BOILER WATER FLOW RATE IN U S GALLONS PER MINUTE PRESSURE DROP IN FEET OF HEAD OF WATER OLD TURBOMAX 23 24 TURBOMAX 23 24 33 34 44 45 TURBOMAX 65 TURBOMAX 109 Domestic Water Side Secondary Circuit Pressure Drop VS Domestic Water Flow rate TURBOMAX Indirect Hot Water Heater 0 2 4 6 8 10 12 14 16 18 0 5 10 15 20 25 30 DOMESTIC WATER FLOW RATE IN U S GALLONS PER MINUTE...

Page 33: ...00 feet Quantity Equivalent Feet of Itemdescription Diameter Valves at systemflow rate of Valves Straight Pipe Inches US GPM Feet 100 Feet X X Equivalent Feet 100 Feet of Head Inches US GPM Feet 100 Feet X X Equivalent Feet 100 Feet of Head Inches US GPM Feet 100 Feet X X Equivalent Feet 100 Feet of Head Step 5 System Quantity of Flow rate Friction Loss TURBOMAX Flow rate TURBOMAX through one thro...

Page 34: ... 2 482 2 879 3 305 3 760 4 245 4 759 5 302 5 875 132 65 145 259 404 582 792 1 034 1 309 1 616 1 955 2 327 2 730 3 167 3 635 4 136 4 669 5 235 5 833 6 463 144 71 159 282 441 635 864 1 128 1 428 1 763 2 133 2 538 2 979 3 455 3 966 4 512 5 094 5 711 6 363 7 050 156 76 172 306 477 687 936 1 222 1 547 1 909 2 310 2 750 3 227 3 742 4 296 4 888 5 518 6 187 6 893 7 638 168 82 185 329 514 740 1 008 1 316 1...

Page 35: ...200 13 2 13 8 20 0 20 8 31 1 32 3 220 14 5 15 2 22 0 22 9 34 2 35 5 240 15 9 16 6 24 0 25 0 37 3 38 7 260 17 2 18 0 26 0 27 1 40 4 41 9 280 18 5 19 4 28 0 29 2 43 5 45 2 300 19 8 20 8 30 0 31 3 46 6 48 4 320 21 1 22 1 32 0 33 3 49 7 51 6 340 22 5 23 5 34 0 35 4 52 8 54 8 360 23 8 24 9 36 0 37 5 55 9 58 1 380 25 1 26 3 38 0 39 6 59 0 61 3 400 26 4 27 7 40 0 41 7 62 1 64 5 420 27 7 29 1 42 0 43 8 65...

Page 36: ...200 13 4 13 9 20 1 21 0 31 3 32 4 220 14 7 15 3 22 2 23 0 34 4 35 6 240 16 0 16 7 24 2 25 1 37 5 38 9 260 17 4 18 1 26 2 27 2 40 6 42 1 280 18 7 19 5 28 2 29 3 43 8 45 4 300 20 0 20 9 30 2 31 4 46 9 48 6 320 21 4 22 3 32 2 33 5 50 0 51 9 340 22 7 23 7 34 2 35 6 53 2 55 1 360 24 0 25 1 36 3 37 7 56 3 58 3 380 25 4 26 5 38 3 39 8 59 4 61 6 400 26 7 27 9 40 3 41 9 62 5 64 8 420 28 0 29 3 42 3 44 0 65...

Page 37: ...r Water content Quantity TURBOMAX tank US Gallons X US Gallons Boiler s US Gallons X US Gallons Storage tank s US Gallons X US Gallons Other components US Gallons X US Gallons Volume of water in system Total US Gallons Expansion Tank Working Parameters Volume of Diaphragm Tank see Table 6 or Table 7 US Gallons Expansion Tank Brand Model Volume Selection Maximum operating pressure at tank safety re...

Page 38: ...and handling to and from Manufacturer The components repaired or replaced are warranted for the residual period of the initial warranty on the unit Exclusions This warranty is void and shall not apply if 1 Defects or malfunctions resulting from installation repair maintenance and or usage that are not done in conformity with the manufacturer s installation manual or 2 Defects or malfunctions resul...

Reviews: