VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised August 2017)
, Page
52.
4.12 CONFIG. ALARM MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Status:
HL/LWCO alarm
BV_StatusExtAlarm
Displays the external alarm status. The external
alarm contact is activated only if a high limit or low
water level alarm occurs.
0 = Off
1 = On
---
Silence Alarm
WP_SilenceAlarm
Temporarily suspends the alarm .
0 = Off
1 = On
Off
Reset Lockdown WP_ResetLockDown
Cancels the Lockdown mode without resetting the
unit.
Resetting the unit is required when it is in
LOCK-OUT
mode
, following repeated alarms over a short period.
0 = Off
1 = On
Off
Internal buzzer
WP_ActivateInternalBuzzer
Activates the controller’s internal buzzer.
0 = Off
1 = On
On
Deactivate LL
alarm
WP_DeactivateAlarmLL ()
Deactivates the LL alarm.
0 = Off 1 = On
Off
4.13 OCCUPATION MENU SETTINGS
Display
BACnet Variable
Description
Possible Settings
Default
Occupation
Mode
WP_ActivateOccupationMode
Activates the Occupation function.
0 = Off
1 = On
---
Source OCC
WP_SourceOccupation
Selects the source
used to determine the building’s
occupation schedule.
0 = Schedule
1 = Contact OCC
Lowering T.
WP_LoweringTInnoccupation
Lowers the set-point temperature.
---
Off
Occupation
Status
BV_StatusOccupation
Displays the Occupation mode status.
Off: Day mode; the set-point temperature is not
lowered
On: Night mode; the set-point temperature is lowered
according to the configuration
0 = Off
1 = On
On
Force Day Mode WP_ForceOccupationDay
Forces the Day mode. The set-point temperature will
not be lowered.
0 = Off ; 1 = On
Off