VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised August 2017)
, Page
37.
This mode operates with the
Fixed Set-point
and
Outdoor reset mode
.
This menu allows the Boost mode to be
activated, this mode increase the set-point
temperature when the heating load of the
building exceeds the capacity generated by the
current water temperature determined by the
boiler.
This mode is activated after a period of 30 min if
the heat demand is maintained for 30
consecutive minutes on W1. After this period,
the set temperature will start to rise until a
predetermined maximum temperature is reached
depending on the heating mode until the
demand is filled. This temperature increase is
temporary and has a maximum duration of 120
minutes or when the request is terminated on
W1.
N.B. The
BOOST
mode is particularly interesting
for applications such as:
o
Applications with a programmable thermostat
with automatic lowering of the building
temperature.
o
Return to normal heat demand after a
prolonged period of sunshine where there
have been no long-term demands and,
therefore, heating floors will take a long time
to provide heat at d Normal water.
4.3.11
WARM WEATHER SHUTDOWN
Shuts down the boiler when the outside
temperature reaches an established
threshold.
This mode
stops the boiler’s heating production
when the outside temperature is higher than a
pre-determined temperature (ex: 68°F).
Note: If the boiler is configured with DHW mode,
it will continue to operate normally in order to
meet the DHW heating demand.
4.3.12 CHANGE PASSWORD
Changing the password
This menu allows you to change the installer
account password
4.4 INTERNET
The settings available on the controller are also
available remotely on a web portal. This portal
works only when the boiler is properly connected
to an internet or Ethernet network. The various
setting parameters and the protocol for
connecting the boiler to a network are available
in the
Communication menu
and
Section
4.3.8
.
4.4.1
WEBSITE
In order to access the boiler remotely via the
internet, the boiler controller must be correctly
connected.
The web portal has 3 main menus, the
User
,
Installer
and
Manufacturer
menu. The structure
of the web portal is the same as the controller;
please refer to the previous sections, if you have
any questions.
Ex: The user can obtain information concerning
the boiler status, in the menu Operations /
N.B. The password to acces the installater
section of the website is 1111. He is
independent of the boiler password
.
4.4.2 EMAIL
In order to configure the alarm by e-mail, you
must:
1. You must first ensure that you enter the
correct
information
in
the
controller
(depending on your network) under the
following options:
a. IP address
b. Default Gateway
c. Subnet mask
d. Primary DNS
e. Secondary DNS
You must restart the device for the changes
to take place.
2. Access the Boiler Web Portal.
3. Click on the Installer / Communication
menu.