INSTALLATION
INSTALLATION
UNPACKING THE PRODUCT
T
TBPS KOMPACT
solar heaters are supplied in a
single package on a wooden pallet.
The boiler comes with a solar station supplied with solar reg-
ulator already wired to the high-efficiency circulator, and two
non-wired probes to be inserted in the boiler sockets.
The following items are delivered in a plastic bag inside the
packaging:
- Instruction manuals
- Bar code label
- Hydraulic test certificate
- Energy label (to be applied to device upon installation)
- No. 1 solar probe PT1000
- No. 2 probes NTC.
b
The instruction manual is an integral part of the solar stor-
age cylinder. Once located, read it thoroughly and keep
it safe.
b
For handling operations, thoroughly follow the instruc-
tions on device package label.
ACCESS TO THE SOLAR STATION
To access the solar station it is necessary to remove the solar
regulator covering (1) and then the front insulation (2).
1
2
PLACE OF INSTALLATION
T
TBPS KOMPACT
storage cylinders can be in-
stalled in any room where there is no specific requirement for
an electrical protection rating higher than IP X0D.
≥ 0,3 m
≥ 0,8 m
≥ 0,3 m
≥ 0,8 m
≥ 0,7 m
NOTE:
the above-indicated dimensions are recommended for
a correct maintenance and access to the device.
b
When installing the boiler, allow sufficient space around
it to access all safety and control devices and to permit
easy maintenance.
INSTALLATION IN OLDER SYSTEMS AND
SYSTEMS REQUIRING MODERNISATION
When installing
T
TBPS KOMPACT
storage cylin-
ders in old systems or systems requiring modernisation, al-
ways perform the following checks.
- Make sure that the system is fitted with safety and con-
trol devices in accordance with applicable legislation
and standards
- Make sure that the central heating circuit has been
flushed out to remove all sludge and lime scale, and
has been vented and seal tested
- Make sure that a suitable water treatment system is
installed if the quality of the supply/recirculation water
so demands (refer to the reference values listed in the
table alongside).
WATER QUALITY REQUIREMENTS
REFERENCE VALUES
pH
6-8
Electrical conductivity
less than 200 μS/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0.3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 35°F
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm
The values above ensure proper operation of the system. Refer
to the limit values specified in the current standards and regu-
lations on the installation site.
Installation