ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)

Supply power wire A:

Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire 

must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between 

the fixing point and the terminals allows the straining of the conductors L, N  before that of the grounding. 

Connecting wire B (SHIELDED):

Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”. 

The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).

Connecting wire C (with ground conductor):

Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The 

wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).

LENGTH, SIZE  WIRES AND  DELAYED FUSE

  

NARROW TUBE 

LARGE TUBE

 

MODEL (INDOOR UNIT)

 

 

OUTER DIAMETER 

MIN. THICKNESS 

OUTER DIAMETER 

MIN. THICKNESS

 

6,35 mm 

0,8 mm 

9,52 mm 

0,8 mm

 

B - C 

6,35 mm 

0,8 mm 

12,7 mm 

0,8 mm

Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed 
polyethylene (min. thickness 8mm).

l

 

PVC pipe for condensate drain pipe (ø int.18mm)  in length suitable to let the condensate flow into the outside drainage.

l

 

Anti-freeze oil for flare connections (about 30g.).

l

 

Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.

4

Supply power wire A:

Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire

must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between

the fixing point and the terminals allows the straining of the conductors L, N  before that of the grounding.

Connecting wire B (SHIELDED):

Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”.

The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).

Connecting wire C (with ground conductor):

Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The

wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).

MODEL

mm

2

2 UNITS

1 UNIT

L ("C") m

1,5

15

0,75

≤ 25

1,5

≤ 25

L ("A") m

L ("B") m

15

≤ 20

≤ 20

 10 A

LENGTH, SIZE  WIRES AND  DELAYED FUSE

ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)

NARROW TUBE

LARGE TUBE

MODEL (INDOOR UNIT)

OUTER DIAMETER

MIN. THICKNESS

OUTER DIAMETER

MIN. THICKNESS

A

6,35 mm

0,8 mm

9,52 mm

0,8 mm

B - C

6,35 mm

0,8 mm

12,7 mm

0,8 mm

l

Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene

(min. thickness 8mm).

l

PVC pipe for condensate drain pipe (ø int.18mm)  in length suitable to let the condensate flow into the outside drainage.

l

Anti-freeze oil for flare connections (about 30g.).

l

Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.

TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS

L Tot. (m)

L n (m)

L Tot. (m)

L n (m)

1 UNIT

7,5

-

20

-

AFEX 050

2 UNIT

15

12

30

25

AT SHIPMENT

ADDITIONAL REFRIGERANT

L Tot. =  Total tubing length (L1 + L2 + L3...)

Ln =

Maximum tubing length of a single indoor unit (n=1,2,3...)

REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT

For tubing 1/4 “ - 3/8” = 15g/m

For tubing 1/4 “ - 1/2” = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4)

LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
No additional charge of compressor oil is necessary.

EG

L Tot. =  Total tubing length (L1 + L2 + L3...)

Ln = 

Maximum tubing length of a single indoor unit (n=1,2,3...)

REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT

For tubing 1/4 “ - 3/8” = 15g/m

For tubing 1/4 “ - 1/2” = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4)

LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)

No additional charge of compressor oil is necessary.

 

4

Supply power wire A:

Multipolar electric wire. Size and length of the suggested electric wire are showed on table “electrical data”. The wire

must be Mod. H07RN-F (according to CEI 20-19 CENELEC HD 22). Make sure the length of the conductors between

the fixing point and the terminals allows the straining of the conductors L, N  before that of the grounding.

Connecting wire B (SHIELDED):

Bipolar electric shielded wire; size and length of the suggested electric wire are showed on table “electrical data”.

The wires have not to be lighter than Mod. H05VVC4V5-K (according to CEI 20-20 CENELEC HD21).

Connecting wire C (with ground conductor):

Multipolar electric wire; size and length of the suggested electric wire are showed on table “electrical data”. The

wires have not to be lighter than Mod. H07RN-F (according to CEI 20-19 CENELEC HD22).

MODEL

mm

2

2 UNITS

1 UNIT

L ("C") m

1,5

15

0,75

≤ 25

1,5

≤ 25

L ("A") m

L ("B") m

15

≤ 20

≤ 20

 10 A

LENGTH, SIZE  WIRES AND  DELAYED FUSE

ADDITIONAL MATERIAL REQUIRED FOR INSTALLATION (NOT SUPPLIED)

NARROW TUBE

LARGE TUBE

MODEL (INDOOR UNIT)

OUTER DIAMETER

MIN. THICKNESS

OUTER DIAMETER

MIN. THICKNESS

A

6,35 mm

0,8 mm

9,52 mm

0,8 mm

B - C

6,35 mm

0,8 mm

12,7 mm

0,8 mm

l

Deoxidized annealed copper tube for refrigerant tubing connecting the units of the system; it has to be insulated with foamed polyethylene

(min. thickness 8mm).

l

PVC pipe for condensate drain pipe (ø int.18mm)  in length suitable to let the condensate flow into the outside drainage.

l

Anti-freeze oil for flare connections (about 30g.).

l

Electric wire: use insulated copper wires of size and length as shown at paragraph “SYSTEM WIRING DIAGRAMS”.

TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS

L Tot. (m)

L n (m)

L Tot. (m)

L n (m)

1 UNIT

7,5

-

20

-

AFEX 050

2 UNIT

15

12

30

25

AT SHIPMENT

ADDITIONAL REFRIGERANT

L Tot. =  Total tubing length (L1 + L2 + L3...)

Ln =

Maximum tubing length of a single indoor unit (n=1,2,3...)

REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT

For tubing 1/4 “ - 3/8” = 15g/m

For tubing 1/4 “ - 1/2” = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4)

LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
No additional charge of compressor oil is necessary.

EG

TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS

8

 

Summary of Contents for AFEX 050 MONO

Page 1: ...ENGLISH ITALIANO AFEX 050 MONO ISTRUZIONI D INSTALLAZIONE INSTALLATION INSTRUCTIONS Unit esterna Outdoor unit...

Page 2: ...o con i tubi refrigeranti il compressore o le parti mobili del ventilatore Nel collegare l alimentazione e le linee di controllo non usare cavi a pi conduttori Usare cavi separati per ciascun tipo di...

Page 3: ...possibilmente in ombra e leggermente ventilate Fissare l unit alla base di appoggio per evitare vibrazioni Predisporre l unit esterna su base solida rialzata dal terreno e fissarla con 4 bulloni a esp...

Page 4: ...RNO SPESSORE MINIMO A 6 35 mm 0 8 mm 9 52 mm 0 8 mm B C 6 35 mm 0 8 mm 12 7 mm 0 8 mm l Tubo in rame ricotto e disossidato per refrigerazione per il collegamento tra le unit ed isolato con polietilene...

Page 5: ...E DI CONFORMIT Questo prodotto marcato in quanto conforme alle Direttive Bassa Tensione n 2006 95 CE Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 with EN 60335...

Page 6: ...ing to touch the refrigerant tubing compressor or any moving parts of the fan Do not use multi core cable when wiring the power supply and control lines Use separate cables for each type of line When...

Page 7: ...lug bolts or equal to bolt down the unit reducing vibration and noise Provide a solid base for outdoor unit raised from the ground level Fix unit to base using 4 anchor bolts 10 cm 10 cm 40 cm SYSTEM...

Page 8: ...lare connections about 30g l Electric wire use insulated copper wires of size and length as shown at paragraph SYSTEM WIRING DIAGRAMS TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS L Tot m L n m L Tot...

Page 9: ...ge 10 DECLARATION OF CONFORMITY This product is marked as it satisfies Directives Low voltage no 2006 95 EC Standard EN60335 2 40 2003 incl Corr 2006 A11 2004 A12 2005 A13 2012 A1 2006 A2 2009 con EN...

Page 10: ...T INTERNE N 2 INDOOR UNITS AFEX 050 MONO SOLO ONLY AFEX 050 MONO AFEX 050 MONO SOLO ONLY AFEX 050 MONO EMIX PORT VEDI IL MANUALE D INSTALLAZIONE DEL AF ACS O AF ACS B EMIX PORT SEE AF ACS OR AF ACS B...

Page 11: ...8 mm Insulation Utilizzare del tubo in rame isolato Tagliare con lunghezza maggiorata di 30 50 cm oltre la distanza tra le unit Use insulated copper tube Cut approximate 30 50 cm longer than actual d...

Page 12: ...ubes Hold the tube end downward and be sure that no dirt falls into the tube EN I F Cartellare le estremit dei tubi ricordandosi di infilare i bocchettoni rimossi dalle unit Insert flare nuts removed...

Page 13: ...efrigerant tubes Connect the vacuum pump to the outside unit as shown in the figure Air and moisture have undesiderable effects on the refrigerant system VACUUM PUMP CAPACITY 100 h Tubing length Tubin...

Page 14: ...e service valve on small tube then close it after 10 seconds Check tightness of all joints using liquid soap EN I L Valvola a 3 vie bassa pressione Wide tube service valve 3 way Action Valvola a 2 vie...

Page 15: ...ircuito Le due unit interne vanno contraddistinte in unit interna A ed unit interna B Verificare che il collegamento idraulico all unit interna A o B corrisponda il suo corretto collegamento elettrico...

Page 16: ...NUALE INSTALLAZIONE DELL UNITA INTERNA SPECIFICA BEFORE STARTING THE SYSTEM IT IS NECESSARY TO SET THE REFRIGERANT CIRCUIT ADDRESSES THE SETTING HAS TO BE MADE ON THE INDOOR UNITS AND FOR EACH INDOOR...

Page 17: ...manifold to the charge port on a wide tube service valve partially open it 1 4 turn Let the air purge from the manifold Fully close the narrow tube service valves all the way Rimuovere il gruppo manom...

Page 18: ...18...

Page 19: ...19...

Page 20: ...perfezionamento di tutta la sua produzione le caratteristiche estetiche e dimensionali i dati tecnici gli equipaggiamenti e gli accessori possono essere soggetti a variazione As part of the company s...

Reviews: