![Thermia Expansion module 1 Installation Manual Download Page 8](http://html.mh-extra.com/html/thermia/expansion-module-1/expansion-module-1_installation-manual_1104064008.webp)
2.4
Hardware specifications
Hardware specifications
Power supply
24V AC ± 15%, 50...60Hz or 20...36V DC
Ambient hydration
Max. 95% RH
Enclosure
Polycarbonate, PC
Communication
RS485 Modbus/RTU
Operating system
EXOreal C
Ambient temperature
0...50°C
Battery backup
Memory and real time clock, at least 5 years
Storage temperature
-20...+70°C
Display
Background lit LCD, 4 rows with 20 alphanumeric
Power consumption
4VA
Digital inputs (DI)
Potenial free contact, 24V DC (+C)
Analogue inputs(AI, UI)
0...10V DC, PT1000. Selected by software
24 V DC-supply (+C)
0,15A, short circuit protected (DI)
Analogue outputs (AO)
0...10V DC, 5 mA, 12-bit D/A, short circuit protected
Digital output (DO)
Potential free contact via RELAY module RM6 ( 230V, 10A)
1
Dimensions (mm)
335x455x15
Weight (kg)
5
1
Electronic circulation pumps may require external relay due to initial power rush.
Installation Guide
Expansion module 1
VQILV502
Thermia Värmepumpar
8