10.4
Filling and bleeding the brine system
10.4.1
Introduction
Caution
Before filling the brine system, the electrical installation must be completed so that it is possible to operate
the brine pump.
Caution
Before filling the brine system for Atria Optimum Atria Duo Optimum the water heater MUST be filled.
Caution
Always check local rules and regulations before using anti-freeze.
N
Anti-freeze with corrosion protection additives must be used and mixed to achieve frost protection down to
-17 ±2°C for Diplomat, Diplomat Duo and Comfort Optimum.
N
Use only of Thermia recommended ethylene glycol as anti freeze for Atria Optimum and Atria Duo Optimum
mixed to achieve frost protection down to -32±1°C.
Installation Guide
Domestic heat pumps
Thermia Värmepumpar
VMGFP202
61